Installation

Installation
• This unit may be installed suspended from the ceiling or mounted on the wall.
• This unit may only be installed horizontally , as shown in the diagram below. (Side B is facing up) However, it may
be freely installed in any direction, forward or backward, and to the sides.
• Be sure to secure a 600mm square opening for service and inspection as shown in the diagram below, for both
ceiling - suspended installation and wall-mounted installation.
• BD unit does not require drain treatment as it uses internal insulation.
• Service direction is the side B and C
• The piping for the indoor unit may be led around in direction A
• The inclination of side B must be within ±5 degree forward or backward or to the sides.
A
Suspension bolt pitch.
(36)
50
50
50
(56)
50
50
50
90 Multi type Air Conditioner
245
Main Pipe
432
72
300
Branch Pipe
Cover Control
Ø19.05
Ø9.52
(LEV service)
B
30
50
60
C
(Controller service)
(Servicing space)
Min 400
Min 400
(Side view)
Inspection opening
600
(Bottom view)