Electrical Panel; Control And Safety Devices - Western Airconditioning Zeta Echos Technical Information Manual

Zeta echos air/water chillers and heat pumps

Advertisement

TECHNICAL FEATURES

ELECTRICAL PANEL

The panel consists of:
• Main disconnect switch;
• Fuses for main and auxilliary power circuit protection ;
• Magnetothermic switches, pumps (if present);
• Compressor remote switches;
• Fan remote switches ;
• Pump remote switches (for ST version)
• Microprocessor to control the following functions:
- Control of ingoing water temperature;
- Anti-freeze protection;
- Compressor operation timers;
- Automatic rotation of compressor start-up sequence;
- Alarm signals;
- Alarm reset;
- Capacity steps;
- Cumulative alarm contact for remote signaling;
- Forced capacity reduction according to pressure limits;
• Display of:
- Ingoing and outgoing water temperature;
- Currently set temperature and differential;
- Alarm description;
- Hour counter for compressor operation;
• Black box function;
- Power supply (V/ph/Hz): 400/3~/50 ±5%.

CONTROL AND SAFETY DEVICES

• cooled water temperature control probe (on evaporator intake);
• anti-freeze probe on evaporator outtake;
• manual reset high pressure controller;
• controlled manual reset low pressure switch;
• high pressure safety valve;
• compressor overtemperature protection;
• fan overtemperature protection;
• vane actuated mechanical flow switch (supplied as standard)
TESTING
The units are factory-tested and supplied complete with oil and refrigerant.
Western Airconditioning B.V. reserves the right to alter specifications