Zeta echos air/water chillers and heat pumps

Advertisement

EC FANS
Units can be couples to the innovative direct current EC axial fans with electronically commutated
brushless motor.
Theses motors with permanent magnets rotor ensure a high level of efficiency for all work conditions
and allow to obtain a 15% saving per fan.
Moreover, through a 0-10V analogical signal sent to every fan, the microprocessor allows to control
the condensation through continuous air flow regulations on variation of the outdoor air temperature
and the consequent sound emission reduction.
"BRINE KIT"ACCESSORY
It is applied if the evaporator output temperature is included within +3°C and
-8°C. It consists in a higher thermal insulation of the exchanger and piping, a specific calibration of the
low pressure switches and of the anti-freeze alarm, and dimensioning check of the mechanical
thermostatic valve.
If it is not included in the set-up, the "Check condensation" accessory must be added.
ELECTRONIC THERMOSTATIC VALVE
The use of this accessory is particularly indicated for units that operate in very unstable heat load
conditions or in unstable functional mode, as in the case of joint management of air conditioning and
production of high temperature water. Use of the electronic thermostatic valve in fact allows to:
 Maximize the heat exchange to the evaporator
 Minimize response times on load variation and on operative conditions
 Optimize the regulation of the over-heating
 Guarantee maximum energy efficiency
SELF-ADAPTABLE REGULATION LOGIC
This function allows the unit control the dynamically vary the outlet waters set point according to the
stop and functional cycles of the machine: in practice, by increasing an reducing the water outlet
temperature, the control avoids that compressor start-ups are too close in time, decreasing the
number of peaks and protecting the unit components.
SOFT-STARTER
Blue Box units adopt all the required functioning set-ups and logics to minimise peak currents. The
Soft-Starter accessory allows a further 40% reduction of normal current peaks, through an electronic
control of the electric motor start-up.
COMPENSATION OF THE SET-POINT to the external air temperature
The unit microprocessor control can compensate the set point in an dynamic way, on variation of the
external air temperature. The compensation can be positive or negative: with positive compensation,
on increase of the air temperature the functioning set also increases. With negative compensation on
increase of the air temperature the set decreases. Compensation can be made either on the summer
set point or on the winter set point (heat pumps).
By default, both summer an d winter negative compensation is set, but this configuration can be
modified from the microprocessor keyboard. Unless otherwise specified, default values are indicated
in the graphics below.