Air For Combustion And Ventilation; Unconfined Space; Confined Space - Bryant 373LAV Installation, Start-Up, And Operating Instructions Manual

Downflow/horizontal gas-fired induced-combustion furnaces series e
Table of Contents

Advertisement

When a furnace is installed in public garages, airplane hangars, or
other buildings having hazardous atmospheres, the unit must be
installed in accordance with the recommended good practice
requirements of the National Fire Protection Association, Inc.
II. AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3 of the NFGC, Air for
Combustion and Ventilation, or applicable provisions of the local
building codes.
Canadian installations must be installed in accordance with NSC-
NGPIC and all authorities having jurisdiction.
CAUTION: Air for combustion must not be contami-
nated by halogen compounds, which include fluoride,
chloride, bromide, and iodide. These elements are found
in aerosol sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household products.
CAUTION: The operation of exhaust fans, kitchen ven-
tilation fans, clothes dryers, or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST be provided for the ventilation
devices, in addition to that required by the furnace.
All fuel-burning equipment must be supplied with air for combus-
tion of the fuel. Sufficient air MUST be provided to ensure there
will not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between the furnace
cabinet and the return-air duct to avoid pulling air from the burner
area and draft safeguard opening.
The requirements for combustion and ventilation air depend upon
whether the furnace is located in an unconfined or confined space.
A. Unconfined Space
An unconfined space must have at least 50 cu ft for each 1000
Btuh of input for all the appliances (such as furnaces, clothes
dryer, water heaters, etc.) in the space.
For Example:
373LAV FURNACE
INPUT BTUH
46,000
69,000
92,000
115,000
135,000
If the unconfined space is constructed unusually tight, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space. A minimum opening with a total of at least 1 sq in. per 5000
Btuh of total input rating for all equipment must be provided.
Return air must not be taken from the room unless an equal or
greater amount of air is supplied to the room.
B. Confined Space
A confined space has volume less than 50 cu ft per 1000 Btuh of
the total input ratings of all appliances installed in that space. A
confined space MUST have 2 permanent openings, 1 within 12 in.
of the ceiling, and the other within 12 in. of the floor. (See Fig. 2.)
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, assume that wood
MINIMUM SQ FT
WITH
7-1/2 FT CEILING
307
460
613
767
920
—4—
RETURN
AIR
INTERIOR
HEATED
SPACE
SUPPLY AIR
* Minimum opening size is 100 square in. with
minimum dimensions of 3-In.
Minimum of 3-In. when type B-1 vent is used.
Fig. 2—Air for Combustion and Ventilation
(Inside Air)
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.
The size of the openings depends upon whether the air comes from
inside or outside the structure.
1. All air from inside the structure:
a. Each opening MUST have at least 1 sq in. of free area
per 1000 Btuh of the total input for all equipment within
the confined space, but not less than 100 sq in. per
opening. (See Fig. 2.)
For Example:
373LAV FURNACE
INPUT BTUH
46,000
69,000
92,000
115,000
135,000
b. If the building is constructed unusually tight, a perma-
nent opening directly communicating with the outdoors
should be provided. This opening should have a mini-
mum free area of 1 sq in. per 5000 Btuh of total input
rating for all equipment in the enclosure.
c. If the furnace is installed on a raised platform to provide
a return-air plenum, and return air is taken directly from
the hallway or space adjacent to the furnace, all air for
combustion must come from outdoors. (See Fig. 3.)
2. All air from outside the structure:
a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq
in. of free area per 4000 Btuh of the total input for all
equipment within the confined space.
VENT THROUGH ROOF
(CATEGORY I)
12" MAX
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
UNCONFINED
SPACE
6" MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
12" MAX
A93387
FREE AREA PER
OPENING (SQ IN.)
100
100
100
115
138

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents