Clearances; Locating Fireplace - White Mountain Hearth DVP36FP30-3 NAT Installation Instructions And Owner's Manual

Direct vent gas fireplace heater
Table of Contents

Advertisement

Clearance to Combustibles
Back
Side
Floor
Top Stand-off
Top Framing Edge
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
Note:** Island (C) and Room
Divider (D) installation is possible
as long as the horizontal portion
of the vent system (H) does not
exceed 20 feet with a minimum
vertical run of 8 feet. See details
in Venting Section.
*When you install your Direct Vent
Fireplace in (D) Room divider or
(E) Flat on wall corner positions,
a minimum of 6 inches clearance
must be maintained from the
perpendicular wall and the front
edge of the appliance.
Page 8

CLEARANCES

0" (0 mm)
0" (0 mm)
0" (0 mm)
0" (0 mm)
3" (76 mm)
Figure 2

LOCATING FIREPLACE

CORNER
INSTALLATION
ANGLED CORNER
INSTALLATION
Mantel Chart (Figure 3)
12" (305mm)
10" (254mm)
15"
(381mm)
13 3/4"
11"
9"
8"
TOP EDGE OF FIREPLACE
Clearances (Figure 4)
Clearance from top of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
CABINET
INSTALLATION
ISLAND
INSTALLATION
ROOM DIVIDER
INSTALLATION
Figure 5
MANTEL
COMBUSTIBLE TRIM AND MANTELS
8"
ALLOWED IN SHADED AREA
6"
4 ½"
3 3/4"
3"
2 1/4"
1 ½"
3/4"
7"
6"
5"
4"
3"
Figure 3
Figure 4
FLUSH WALL
INSTALLATION