Honeywell T7200D Product Data page 13

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Installer
Setup Number
(Press
Unoccupied
Temp key
to change)
Select
Interstage
31
control point
(T7300F,
Q7300C,D
only).
Minimum on-
32
time (T7300F).
Minimum off -
33
time for the
compressor.
Temperature
34
range stops in
heating
(T7300F).
Temperature
35
range stops in
cooling
(T7300F).
Not used.
36
Temperature
37
display
adjustment.
Minimum off-
38
times in heating.
Not used.
39
Installer Setup
40
lockout (keypad
lockout is
enabled and
disabled by DIP
switch 1 on
back of
thermostat).
Table 8. Thermostat Installer Setup Options (Continued).
Factory Setting
Display
Description
0
Disabled.
2
2-minute minimum on-
time for heating and
cooling.
4
4-minute minimum off-
time for the
compressor.
90
Highest heating
setpoint.
45
Lowest cooling
setpoint.
0
No difference in
displayed temperature
and actual room
temperature.
4
4—4-minute minimum
off-time
0
0—No Installer Setup
lockout.
Other Choices
(Press
or
Display
1 thru 12 Temperature has to change more
than the chosen value before the
system calls for the next stage.
(Example: 68°F (20°C) is the heat
setpoint, 2°F (1.1°C) is the
interstage setting, temperature is
65.5°F (18.5°C), the second stage
turns on, brings the temperature to
66°F (19°C) and turns off. The heat
pump continues to run until the
setpoint is met.
0 or 1
No minimum on-time or
1-minute minimum on-time for
heating and cooling.
0, 1, 2, 3
Minimum number of minutes
or 5
(0 thru 5) the compressor is off
between calls for the compressor.
40 to 89 Temperature range (1°F
increments) for heating setpoint.
46 to 99 Temperature range (1°F
increments) for cooling setpoint.
1 thru 6 1—Display adjusts to 1°F (0.6°C)
higher than actual room
temperature.
2—Display adjusts to 2°F (1.1°C)
higher than actual room
temperature.
3—Display adjusts to 3°F (1.7°C)
higher than actual room
temperature.
4—Display adjusts to 1°F (0.6°C)
lower than actual room
temperature.
5—Display adjusts to 2°F (1.1°C)
lower than actual room
temperature.
6—Display adjusts to 3°F (1.7°C)
lower than actual room
temperature.
0, 1, 2, 3,
Minimum number of minutes
or 5
(0 thru 5) the heating equipment is
off between calls for heat.
1
1—Installer Setup lockout
activated.
13
key to change)
Actual
Setting
Description
63-4355—2