Honeywell T7200D Product Data page 12

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Installer
Setup Number
(Press
Unoccupied
Temp key
to change)
Select
Displaying
15
temperature
(T7300F only).
Clock format.
16
Intelligent Fan™
17
operation.
Auxiliary contact
18
operation.
Extended fan
19
operation in
a
heating
(T7300F only).
Extended fan
20
operation in
cooling (T7300
only).
Fan key adjust-
21
ment (models
with Fan key).
Remote sensing.
22
Temperature
23
averaging
b
network
(T7300
only).
Not used.
24
Keypad lockout
25
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on
back of
thermostat).
Duration of
26
temporary
override.
Not used.
27 thru 29
Deadband
30
(T7300F only).
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
63-4355—2
Table 8. Thermostat Installer Setup Options (Continued).
Factory Setting
Display
Description
0
Temperature is
displayed.
0
12-hour clock format.
2
Fan operates con -
tinuously in Occupied
and recovery modes.
Fan operates with call
for heating or cooling in
Unoccupied mode.
0
0—Time of day
contact.
0
No extended fan
operation after the call
for heat ends.
0
No extended fan
operation after the call
for cool ends.
0
Fan setting key is
operational.
0
Remote sensing not
activated.
0
Temperature averaging
disabled.
0
No lockout.
3
3—Three hour
override.
2
Heating and cooling
setpoints can be set no
closer than 2°F (1.1°C).
Other Choices
(Press
or
Display
1
Temperature is not displayed.
1
24-hour clock format.
0 or 1
0—Fan only operates with calls for
heating or cooling in Occupied
and Unoccupied modes.
1—Fan operates continuously in
Occupied mode. Fan operates
with calls for heating or cooling
in Unoccupied mode.
0 or 1
1—Economizer contacts.
1
Fan operation is extended
90 seconds after the call for
heat ends.
1
Fan operation is extended
90 seconds after the call for
cool ends.
1
Fan setting key is Auto only.
1
Remote sensing activated.
1
Temperature averaging between
local sensor and remote sensor(s)
activated.
1 or 2
1—Lockout all keys on thermostat
except system and fan settings,
temporary setpoint, clock and
day adjustments, increase
decrease keys.
2— Lockout all keys except Set
Current Day/Time, increase
and decrease
3—Lockout all keys except
Temporary Occupied and Set
Current Day/Time (for clock, day
adjustment).
1, 8 or 12 1—One hour override.
8—Eight hour override.
12—Twelve hour override.
3 thru 10 Heating and cooling setpoints can
be set no closer than the chosen
value.
12
key to change)
Actual
Setting
Description
and
keys.
(continued)