Midea MFA-76CRN1 Technical Manual page 119

R410a tropical split type indoor / outdoor units air conditioner
Hide thumbs Also See for MFA-76CRN1:
Table of Contents

Advertisement

R410A Tropical Split Type Technical Manual
Low pressure protection
Judge 1: The wiring between the low pressure switch and main
control board is connected well or correctly
Judge 2: Whether the low pressure switch is broken
Validate: Short connect the low pressure switch
socket, check whether the system can run normally
Check whether the refrigerant system is ok
Judge 3: Check whether the outdoor ambient temperature is too low
Judge 4: The refrigerant of the system is leakage
Validate: Connect the pressure gauge to the gauge joint of the
system, check whether the pressure is lower than 0.15MPa
Judge 5: The refrigerant pipe is blocked
Replace outdoor PCB
Outdoor Units
Yes
No
No
No
Yes
No
No
Connect it well
Yes
Replace low pressure switch
Yes
Leak hunting: charge nitrogen or
refrigerant to the system, if the
Yes
leakage is serious, there will be
distinct gas leakage "cici" sound;
if the leakage is little, use the
suds(mixture of water and
abluent is also ok, if it can make
bubble) or electronic leak
detector.
Drop refrigerant, then use the high
pressure nitrogen or refrigerant to blow
pipe, vacuumize and add the refrigerant
again
Troubleshooting
Stop the unit
119