Reversing Valve Control Circuit - Hitachi RAS-35FH6 Service Manual

Dc inverter (wall type) type
Table of Contents

Advertisement

8. Reversing valve control circuit

Reversing
valve
DC voltmeter
or multimeter
Reversing valve control circuit will switch reversing valve ON/OFF (cooling ON) according to instruction
from indoor microcomputer depending on the operation condition shows in Table 8-1.
Voltage at Q701 (between Collector and Emittor) in each operation condition is approximately as shown
in Table 8-1 when measured by multimeter.
Cooling
Heating
Dehumidifying
Power P.W.B.
CN2
2
D701
4
Q701
R705
R706
V
D-0V
Table 8-1
Operation condition
General operation of cooling
In normal heating operation
MAX. rotation speed instructed by indoor
microcomputer after defrost is completed
Defrosting
Sensor dry
C-35V
MAIN P.W.B.
12V
R701
PQ701
CN4A
CN4B
6
6
Fig. 8-1
Collector voltage of Q701
– 54 –
Microcomputer
24
About 0.8V
About 35V
About 35V
About 0.8V
About 0.8V