Dimensions — outdoor units
DIMENSION CHART
UNIT WITH
UNIT
ALUMINUM-FIN COIL
38AQS
Dim. A
Dim. B
1'-8"
008
[508.0]
[431.8]
SERVICE VALVE CONNECTIONS
UNIT 38AQS
SUCTION
" [28.6]
1
008
1
/
8
ELECTRICAL CONNECTIONS
CONNECTION SIZES
" Dia. [35] Field Power Supply Hole
AA 1
3
/
8
BB 2" Dia. [51] Power Supply Knockout
" Dia. [64] Power Supply Knockout
1/ 2
CC 2
" Dia. [22] Field Control Wiring Hole
DD
7
/
8
12
UNIT WITH
COPPER-FIN COIL
Dim. A
Dim. B
"
"
1'-5"
1'-9
1
/
1'-4
3
/
2
4
[546.0]
[425]
LIQUID
" [12.7]
1
/
2
38AQS008
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of gravity. See Chart for dimensions.
3.
Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail).
a. Bottom to combustible surfaces: 0 in.
b. Outdoor coil, for proper airflow: 36 in. one side, 12 in. the other. The
side getting the greater clearance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units: Control box side, 42 in. per NEC.
e. Between unit and ungrounded surfaces: Control box side, 36 in. per
NEC.
f. Between unit and block or concrete walls and other grounded sur-
faces, control box side, 42 in. per NEC.
5. With the exception of the clearance for the outdoor coil as stated in
note 4b, a removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or class
A, B, or C roof covering material.