PFC-6075 Fire Alarm Control Panel Installation, Operation, & Programming Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 • Technical Support: (866) 956-1211 • Fax: (314) 595-6999 www.pottersignal.com Manual #5403593–Rev C 2/13...
WARRANTY INFORMATION The essential purpose of any sale or contract for sale of any of the products listed in the POTTeR catalog or price list is the furnishing of that product. It is expressly understood that in furnishing said product, POTTeR does not agree to insure the Purchaser against any losses the Purchaser may incur, even if resulting from the malfunction of said product.
PFC-6075 • 5403593 • Rev C • 2/13 Table of Contents Section 1: Introduction ..........................1-1 Purpose of This Manual ..........................1-1 System Overview ............................1-1 System Features ............................1-1 P-Link Accessories ..........................1-2 SLC Loop Accessories ........................1-2 Addressable Sensors .........................1-2 Addressable Modules ........................1-2 How to Use this Manual .........................1-3...
Page 4
PFC-6075 • 5403593 • Rev C • 2/13 Notification Appliance Circuits Installation ..................3-24 NAC Wiring .............................3-24 NAC Maximum Wiring Impedance Formula ..................3-24 NAC Wiring Configurations ......................3-24 I/O Circuit Configuration ........................3-26 I/O Circuits as Inputs ........................3-26 I/O Circuits as Outputs ........................3-26 I/O Maximum Impedance Formula ....................3-26...
Page 5
PFC-6075 • 5403593 • Rev C • 2/13 File Save / Save As ..........................5-55 Audit Errors ............................5-55 Uploading History events & Detector (Sensitivity) Status Reports .............5-57 History Reports ..........................5-57 Detector Sensitivity Status Reports ....................5-58 Printing Reports ..........................5-59 Panel Software Overview ........................5-60 Window Regions / Areas........................5-60...
This manual is intended to assist in the installation and programming the PFC-6075 Fire Alarm Control Panel. Refer to this manual to properly install and program the PFC-6075. It is recommended that the user follows the procedures as outlined in this manual to assist in proper installation and prevent damage to the control panel and associated equipment.
PFC-6075 • 5403593 • Rev C • 2/13 Analog / Addressable Sensing Technology Drift Compensation Drift Alert NFPA 72 compliant calibrated smoke test built-in P-Link Accessories RA-6500 or RA-6075 Remote Annunciator – Maximum of 31 per system in any combination UD-1000 Dual Line Fire Communicator –...
How to Use this Manual Refer to this manual before contacting Technical Support. The information in this manual is the key to a successful installation and will assist you in understanding proper wire routing, system requirements, and other guidelines specific to the PFC-6075 system.
PFC-6075 • 5403593 • Rev C • 2/13 Section 2: Before You Start Installation This section addresses information that will help you in completing a successful installation, such as the PFC-6075 cabinet layout, specifications, environmental considerations, and calculating the battery circuit and SLC current draw requirements.
PFC-6075 • 5403593 • Rev C • 2/13 Electrical Specifications Please refer to the table below for electrical specifications: Table 3: System Panel Electrical Specifications Rating I/O Circuits Panel # NACs SLC Power Notes Style and Class per NAC (As Outputs) SLC –...
PFC-6075 • 5403593 • Rev C • 2/13 Main Board Wiring Specifications There are several wiring requirements to consider before connecting circuits to the main board: (1) the circuit separation, and (2) wiring types. Circuit Separation Proper separation between the different types of circuits must be maintained between Power Limited, Non-Power Limited, and High voltage wiring to reduce electrical interferences, transient voltage or voltage ratings.
PFC-6075 • 5403593 • Rev C • 2/13 Cabinet Wiring Connections Optional Figure 2. PFC-6075 Cabinet Wiring UD-1000 DACT High voltage phone connections 120VAC 50Hz-60Hz 240VAC 50Hz-60Hz Connect to separate unswitched AC circuits Optional CA-6075 POWER ALARM EARTH FAULT Class A Expander...
PFC-6075 • 5403593 • Rev C • 2/13 Battery Circuit Calculations Before selecting the battery, it is important to determine the minimum size batteries for standby and alarm times desired for each application and SLC current draw. If the wrong batteries are installed in a specific application or incorrect current draw used, the proper standby and minimum alarm time will not be present.
PFC-6075 • 5403593 • Rev C • 2/13 Isolator Device Load Calculation This section covers the distinction between an addressable sensor and an isolator to correctly calculate the total SLC device load. A device uses an address and consumes power. Whereas, an isolator does not use an address, but does consume power.
PFC-6075 • 5403593 • Rev C • 2/13 Scenario 2: Class B Loop – Isolated Branch Configuration In this configuration, there are 4 separate branches each with an isolation device / module and 1 or more sensors. each sensor requires an address, as shown in Scenario #1 (isolators do not require an address). However, in this scenario, each isolator consumes power equal to 8 devices.
PFC-6075 • 5403593 • Rev C • 2/13 Battery Connections The battery charging circuit is located on the main panel in the lower left portion of the board. The maximum battery charging circuit is 1.0 amp DC; the charging voltage is approximately 27.3 vDC and is supervised.
PFC-6075 • 5403593 • Rev C • 2/13 Section 3: Installation This section addresses installation procedures for SLCs, NACs and optional modules, including the DACT (UD-1000), Class A Card, and Remote Annunciators. Wiring requirements and configuration examples are included throughout this section.
PFC-6075 • 5403593 • Rev C • 2/13 Class A, Style 6 Wiring Configuration Figure 8. Example of Class A, Style 6 Requiring CA-6075 24+ S- S- S+ S- S+ Address No. Address No. Address No. Address No. Potter Electric Signal Company...
PFC-6075 • 5403593 • Rev C • 2/13 Connecting Analog Detectors When installing analog detectors, such as a photoelectric smoke sensor (PSA), photo smoke/fixed heat detector (PSHA), heat detector (FHA), or an analog combination type heat detector (RHA), use detector bases (i.e. AB-6). An analog detector activates its response LeD when activated.
PFC-6075 • 5403593 • Rev C • 2/13 Conventional Initiating Zones (CIZM-4) Class B Figure 12. CIZM-4, Class B From FACP or Select Style B Previous Module Conventional Detector SLC Loop To Next Module 5.1KΩ 1/2W From FACP or EOLR...
PFC-6075 • 5403593 • Rev C • 2/13 Dual Contact Module – 4 inch Mount (DCM-4) Refer to the figure shown below for a Class A DCM-4 wiring example. Figure 15. DCM-4 with One Class A Circuit Note: The resistance of external wiring shall be less that 100Ω.
PFC-6075 • 5403593 • Rev C • 2/13 Monitored Output Module – 4 inch mount (MOM-4) If the power supply connected to the MOM-4 is power limited, then the outputs are power limited. An example of a MOM-4 wired as a conventional application is shown here.
PFC-6075 • 5403593 • Rev C • 2/13 Single Action / Dual Action Pull Station (APS-SA / APS-DA) The APS-SA/DA addressable pull stations are non-coded that provide an addressable point to the panel. The APS pull stations have terminals that allow the SLC to be wired directly to the device and then exit to the next device in the loop. Refer to the wiring example shown below.
PFC-6075 • 5403593 • Rev C • 2/13 Addressing SLC Devices Before devices can be programmed, they must be assigned a unique address. There are two (2) methods to address devices: (1) You may use a hand-held address setting device or (2) Use the panel's System Tools – SLC Addr Prog option. Only authorized system users may access the System Tools options.
Page 29
PFC-6075 • 5403593 • Rev C • 2/13 For a Single Device: From the SLC Addr Prog menu, press 1 to address a Single device. SLC PGM terminals, if not already done. The “Connect Device” prompt displays. Attach connector wires to Connect device.
Notification Appliance Circuits Installation There are two (2) NAC circuits provided on the PFC-6075 rated as continuous 3 amps at 24 vDC. The NAC circuits may be configured for Class A or Class B. (Please refer to the Class A and B wiring examples located in this section.) NAC Wiring Outputs are supervised and regulated.
Page 31
PFC-6075 • 5403593 • Rev C • 2/13 Figure 24. NAC Class A Wiring Example NAC 1 NAC 2 NAC 1 NAC 2 CA-6075 Class A card Notification Appliance DWG #602-5A 3-25...
I/O Circuit Configuration The PFC-6075 is equipped with two (2) I/O circuits that may be configured as either input or output devices. The panel has ground fault detection on the I/O circuits. The impedance to ground for ground fault detection is 0 ohms.
Reverse Polarity Communication Line Circuit Only I/O 1 and I/O 2 on the PFC-6075 can be programmed as reverse polarity circuits. The short circuit current is rated at 24 VDC and 14 mA maximum. Please refer to the figure below for an example of wiring a reverse polarity communication line circuit.
PFC-6075 • 5403593 • Rev C • 2/13 Municipal Box Connection When programmed as a municipal box connection, the circuit power is limited, supervised for open and short circuit conditions, and provides a local energy connection. Figure 27. Municipal Box Wiring Example...
PFC-6075 • 5403593 • Rev C • 2/13 CA-6075 Class A Expander Installation The Class A configuration requires the use of the CA-6075. Once the card is installed, the additional terminals are provided for the return loop of the NAC. The CA-6075 provides the terminals for both NACs, SLCs, and P-Link. Refer to the figures below for examples of installing and wiring a Class A expander card.
PFC-6075 • 5403593 • Rev C • 2/13 P-Link Devices Accessory devices, such as remote and LeD annunciators, and a remote expander (RLY-5) are connected to the main control panel utilizing the four-wire P-Link bus for power and communication. This panel supports a maximum of 64 P-Link devices, which can be connected using a Class B or Class A wiring style (examples are provided throughout this topic).
PFC-6075 • 5403593 • Rev C • 2/13 Figure 31. Example of P-Link Class A Wiring Requiring a CA-6075 CA-6075 Connection P-LINK Panel Connection Expansion P-LINK Device Expansion Device DWG #602-12A P-Link Addresses each P-Link device has a five position dip switch which is used to program the device address ranging from one (1) to thirty- one (31).
PFC-6075 • 5403593 • Rev C • 2/13 Remote Annunciators Installation (RA-6500 and RA-6075) This panel supports up to 31 annunciators in any combination (RA-6500 / RA-6075). The RA-6500 provides a 4 x 40 character LCD display. Whereas, the RA-6075 provides a 2 x 16 character LCD display, along with standard function and numeric keys. All annunciator models listed are designed to be mounted on a flat non-condensing surface or electrical box.
PFC-6075 • 5403593 • Rev C • 2/13 The LeD-16 is controlled over the 4-wire P-Link connection. The higher current required for the LeD outputs can be provided by the panel, or from an auxiliary power source as shown below. The auxiliary power can be any 24vDC source, and is fully supervised.
Page 40
PFC-6075 • 5403593 • Rev C • 2/13 The 50 programmable LED outputs are located on connectors P1-P5, each containing ten (10) LeD outputs and two (2) 5vDC outputs. The system LEDs and PZT control outputs are located on connector P6. LeDs are wired as shown below; no external resistor is required.
PFC-6075 • 5403593 • Rev C • 2/13 Setting Addresses The DRv-50's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range of one to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
PFC-6075 • 5403593 • Rev C • 2/13 Setting Addresses The RLY-5's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range of one to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
PFC-6075 • 5403593 • Rev C • 2/13 Setting Addresses The FCB-1000's address is set by dip switch S1. The address must be set in the range of one (1) to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.) Figure 46.
PFC-6075 • 5403593 • Rev C • 2/13 FIB-1000 Wiring FIB-1000s are installed in pairs. (Please refer to Diagrams #1 & 2 shown below to properly wire the two FIB-1000s.) The first FIB-1000, referred to as "FIB-1000 (A)" below can be installed in any of the compatible fire alarm enclosures, or the FIB- 1000RM.
PFC-6075 • 5403593 • Rev C • 2/13 Setting Addresses The FIB-1000's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range of one to thirty (1–30) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
PFC-6075 • 5403593 • Rev C • 2/13 Setting Addresses A SPG-1000 address is set by dip switch S1. The address must be set in the range of one (1) to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.) Figure 54.
PFC-6075 • 5403593 • Rev C • 2/13 The UD-1000 slides into the guides located at the bottom of the panel, and then secured with screws as shown in the following illustration. Figure 55. Example of an Installed UD-1000 Dialer...
PFC-6075 • 5403593 • Rev C • 2/13 Section 4: Operation This section provides an overview of the control panel’s basic operations, which includes the status LeDs, function pushbuttons, and a Control Panel Menu Tree quick reference sheet. Control Panel Basic Operation The control panel is comprised of a two (2) line x 16-character LCD display panel, arrow keys, push button function keys, status LeDS, and the numeric keypad.
PFC-6075 • 5403593 • Rev C • 2/13 Menu Navigation Keys The arrow keys allow you to scroll or move through the control panel menus. The Enter and Esc keys may also be used to navigate through menus; they are located on the numeric keypad. The table shown below provides a summary of the navigation keys.
PFC-6075 • 5403593 • Rev C • 2/13 The table below provides a brief summary of the pushbuttons: Table 7: Control Panel Pushbuttons Pushbutton Description Press to acknowledge the currently displayed condition. Press to silence all outputs programmed as silenceable and buzzer.
PFC-6075 • 5403593 • Rev C • 2/13 Control Panel Menu Tree This section provides a reference to menu options as they appear on the LCD panel. Appendix G also provides a copy of the menu tree. MAIN MENU 1=View History...
PFC-6075 • 5403593 • Rev C • 2/13 Section 5: Programming This section addresses programming options and their parameters, provides an overview of the programming process, and addresses how to use the two programming methods: (1) the LEARN function, and (2) the remote computer programming process.
Page 53
PFC-6075 • 5403593 • Rev C • 2/13 Table 9: Programming Options Feature or Permitted Setting(s) Permitted Topic Possible Settings Comment Option in UL (Y/N) in UL864? Alarm Supervisory Positive Alarm Sequence Auxiliary Zone Zone Type All settings allowed Fire Drill...
Page 54
PFC-6075 • 5403593 • Rev C • 2/13 Table 9: Programming Options Feature or Permitted Setting(s) Permitted Topic Possible Settings Comment Option in UL (Y/N) in UL864? SLC Point Alarm verif Yes/No All settings allowed SLC Point Supervisory Yes/No All settings allowed...
Note: This approach may eliminate programming errors, however, these are only recommendations. Software Installation It's easy to install the PFC-6075 software and requires only a few minutes to complete. Once done, the program automatically creates a shortcut icon on your desktop for easy access.
PFC-6075 • 5403593 • Rev C • 2/13 LEARN Programming The LeARN mode enables you to efficiently configure all connected, addressed input and output devices. (Refer to Section 3: Installation – Addressing SLC Devices, for detailed instructions.) Only authorized users may access this function.
Page 57
PFC-6075 • 5403593 • Rev C • 2/13 The following series of messages display on the LCD: PFC-6075 Initializing IP PFC-6075 Obtaining IP Notes: • If the ethernet cable is connected to PC, you will see the "Initializing IP" message prior to the "Obtaining IP"...
PFC-6075 • 5403593 • Rev C • 2/13 Transferring Data This section provides step-by-step instructions for completing uploading and downloading data transfers. The "Transfer" icons are located at the top of the Programmer window and are briefly described below. Table 10:...
PFC-6075 • 5403593 • Rev C • 2/13 Uploading from Panel to Computer The Upload Configuration File to Computer transfer icon is used to upload the configuration file from the panel to the computer once the LeARN function is completed or whenever devices are added or removed from the panel.
PFC-6075 • 5403593 • Rev C • 2/13 IP address or panel name in the “Transfer Via IP” field. Enter Notes: • To capture your panel’s unique IP address, disconnect the ethernet cable from panel. The message “Ethernet Lost” displays indicating connectivity is lost. Be prepared to write down the address, and reconnect cable.
PFC-6075 • 5403593 • Rev C • 2/13 File New The File New menu option is used to complete all programming from scratch on the computer. You must select the correct panel model prior to programming. Note: It is imperative that you choose the correct panel model prior to programming or completing any data transfers, otherwise, you cannot complete a successful download to the panel.
Page 62
PFC-6075 • 5403593 • Rev C • 2/13 Downloading a Configuration File To download the configuration file: Download Configuration File to Panel icon or right click from the “Transfers” region, then click “Add”. Click the The Transfer dialog box displays.
PFC-6075 • 5403593 • Rev C • 2/13 Uploading History Events & Detector (Sensitivity) Status Reports The Upload History File to Computer and Upload Detector (Sensitivity) Status to Computer icons allow you to view valuable information that can be essential when analyzing system operations. You may choose to print the History and Detector Status reports by using the Print icon.
PFC-6075 • 5403593 • Rev C • 2/13 Detector Sensitivity Status Reports The Upload Detector Status File to Computer icon allows you to create reports showing sensor sensitivity related settings. This information may be used to troubleshoot detector issues. To transfer detector (sensitivity) status information: Upload Detector Status File to Computer icon or right click from “Transfers”...
PFC-6075 • 5403593 • Rev C • 2/13 Printing Reports The Print icon allows you to print History and Detector Status reports. Double-click the History or Status file listed in the Transfer window prior to clicking the Print icon. An example of the Report window, which displays a History report, is shown below: Figure 78.
PFC-6075 • 5403593 • Rev C • 2/13 Panel Software Overview This section gives you an overview of the Panel Configuration Software. It addresses navigating through the program windows, understanding the purpose of icons and program features, using Window’s conventional editing techniques and other program shortcuts to efficiently configure your system.
PFC-6075 • 5403593 • Rev C • 2/13 Program Icons The panel software uses several standard Windows’ icons, such as the close button and scroll bars. There are others that are unique to the panel software, such as auto hide, and window position which are summarized in the table below:...
PFC-6075 • 5403593 • Rev C • 2/13 Programming Functions Overview The table below gives you a snapshot of the menu order along with a brief description of each. Details for these options are provided on the following pages. Table 12:...
Example of the Panel Configuration Screen User Name / Password The default user name and password is “Potter” as shown below; they can be changed to ensure that only authorized personnel can transfer data to and from the panel. Figure 83.
PFC-6075 • 5403593 • Rev C • 2/13 General System Functions Job Details Site specific information, such as company name, address and phone numbers may be entered in this window. This information is stored in the panel and is used to identify the panel when using e-mail reporting options. Please refer to the figure shown below.
PFC-6075 • 5403593 • Rev C • 2/13 Day/Night Sensitivity Mode and Holiday Scheduling The Sensitivity option allows you to enable the “Day/Night Sensitivity” feature, establish the starting and ending times for “Night” sensitivity, create a “Holiday Schedule”, and choose the days of the week that the site is normally occupied.
PFC-6075 • 5403593 • Rev C • 2/13 User Codes The Users option allows you to create up to ten (10) user code profiles, if needed. each profile may have different access rights, which controls the panel functions a user may access as well as the option to connect to the Facility Management Tool.
“panel serial number". The serial number is the same as the NetBIOS name, and is located on the panel as shown below. Note: Outgoing panel e-mails are routed through a dedicated Potter server. You must make a notation of your panel's outgoing e-mail address in order to send e-mail requests remotely.
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
Page 77
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
Page 79
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
PFC-6075 • 5403593 • Rev C • 2/13 System e-mail communications and functions are intended for informational reporting purposes only. They are intended to be used as a convenience function. e-mail communications should NOT be used as a primary means of reporting emergency information.
PFC-6075 • 5403593 • Rev C • 2/13 System Programming System programming involves defining the function of devices and their relationships to each other, referred to as mapping. You can define behavior characteristics of individual or groups of devices, map devices into zones, and further customize your system using the panel configuration software from a computer.
PFC-6075 • 5403593 • Rev C • 2/13 Mapping Terminology The table below provides mapping terms that may be helpful to you in understanding the mapping concept: Table 15: Mapping Terminology Term Definition Mapping Creating relationships between devices, modules and sensors and defining their behavior.
PFC-6075 • 5403593 • Rev C • 2/13 Table 16: Zone Styles Zone Description System Alarm Used for outputs that will be activated upon any alarm. System Supervisory Used for outputs that will be activated upon any supervisory. System Trouble Used for outputs that will be activated upon any trouble.
Page 84
PFC-6075 • 5403593 • Rev C • 2/13 Table 17: Zone Attributes Attribute Description •y Defines the output pattern of general-purpose NAC circuits in the zone that occurs during alarm conditions. •y Click on drop-down arrow to display and select an option:...
PFC-6075 • 5403593 • Rev C • 2/13 Creating Zones When creating zones, you may create one or more at a time. This section explains this process and includes examples for your convenience. To create a zone: In the Zones window, right click on any zone name. The shortcut menu displays.
PFC-6075 • 5403593 • Rev C • 2/13 Configuring Zones The next step is to customize a zone’s attributes, which includes changing the name, selecting type of zone, and other characteristics (i.e., constant, double time output pattern, latching or non-latching, silenceable, auto-silence timer, etc.).
PFC-6075 • 5403593 • Rev C • 2/13 NAC Functions The four (4) on-board circuits (NACs 1&2, I/O Ckts 1&2) are automatically configured as “General Purpose”, but may be reconfigured and renamed. The I/O circuits have additional configuration options since they may be configured as inputs. Refer to the two (2) tables below for descriptions of the configuration functions.
PFC-6075 • 5403593 • Rev C • 2/13 SLC Functions The SLC configuration options are described in the table below: Table 20: SLC Configuration Functions Function Description Unused SLC point is unused. Addr Detector Photo Photoelectric Sensor (PSA) Addr Detector Photo Heat...
Page 89
PFC-6075 • 5403593 • Rev C • 2/13 To configure points: Click on the Points function to display the "Points Configuration" window. Figure 107. Example of a Configuration Window Note: Click the columns to sort devices by the field selected, i.e., "Name", "Alarm Verification" or "Low Temp Trouble".
Page 90
PFC-6075 • 5403593 • Rev C • 2/13 To configure a range of points: “Function” field. Click the first point to configure from the Press and hold the SHIFT key, then click in “Function” field of last point. Figure 109.
PFC-6075 • 5403593 • Rev C • 2/13 Click on device type from the shortcut menu. In the example shown here, "Addr Detector Photo Heat" has been selected as the device type. Figure 111. Example of Configuring “Selective” Points Adding Points to Zones This section provides procedures and examples of adding points to one or more zones.
Page 92
PFC-6075 • 5403593 • Rev C • 2/13 Points' window to the “Device” window. The selected points display in the Drag and drop selected points from the “Device” window, as shown below. Figure 114. Example of Moving Selected Points into a Zone...
PFC-6075 • 5403593 • Rev C • 2/13 Group by Area You may group information by different fields in many of the program windows. This flexibility is helpful when configuring or viewing a large amount of information, such as all devices, zones or remote annunciators. examples are included for illustration purposes only.
PFC-6075 • 5403593 • Rev C • 2/13 Cross Zone Configurations The purpose of creating cross zones is to ensure that two (2) or more separate zones are activated before an output zone is triggered. Although crossing two (2) zones is the most common configuration, up to eight (8) zones may be combined. In this case, when all the zones that have been crossed are active, the specified outputs will be activated.
Remote Annunciators (RA-6500 and RA-6075) The PFC-6075 supports up to thirty-one (31) remote annunciators in any combination of RA-6500 and RA-6075. each LCD annunciator may be programmed with a unique name to help identify the location of an “off normal” condition.
PFC-6075 • 5403593 • Rev C • 2/13 LED Annunciators (LED-16) The panel supports ten (10) LeD annunciators. The LeD annunciator provides sixteen (16) LeDs, which may be assigned to a specific zone; when that zone becomes active, the LeD will display the alarm, supervisory or trouble conditions. each LeD annunciator also provides five (5) non-programmable system LeDs that annunciate the overall system condition (Power, Earth, Silenced, Alarm, Supervisory and Trouble).
PFC-6075 • 5403593 • Rev C • 2/13 Relay Board (RLY-5) The panel supports up to thirty-one (31) Relay Boards. each RLY-5 provides five (5) Form-C relay outputs which may be individually mapped to any zone. To add and configure a relay board: Select RLY-5 from the system panel.
PFC-6075 • 5403593 • Rev C • 2/13 Fire Communications Bridge (FCB-1000) The panel supports one (1) FCB-1000. The FCB-1000 provides a remotely-located IP connection into the panel, which may be designated as the IP reporting device versus passing through the on-board internet connection.
PFC-6075 • 5403593 • Rev C • 2/13 Serial Parallel Printer (SPG-1000) The SPG-1000 module allows up to 31 serial and/or parallel printers to be used to log system events. Note: Parallel printers must be connected to the DB25 (J1) connector, serial printers to the DB9 (J2) connection.
PFC-6075 • 5403593 • Rev C • 2/13 DACT (UD-1000) each system may have one DACT module or Digital Alarm Communicator Transmitter. The DACT provides notification to a remote monitoring company when alarms, troubles and supervisory conditions occur. Programming options allow you to select separate accounts for test events and alarm, trouble, and supervisory conditions. You may set up telephone parameters, such as number of rings, when and where to send reports by specifying phone numbers and other report output options.
Page 101
PFC-6075 • 5403593 • Rev C • 2/13 To add and configure a DACT module: Select the Dialer function from the system panel. Click the Add Device button. The “Add Dialer” window displays. Figure 134. Example of Add Dialer Window In the “Phone Line 1 and Phone Line 2”...
PFC-6075 • 5403593 • Rev C • 2/13 Section 6: PSN-1000 / PSN-1000(E) – Installing, Operating & Programming The PSN-1000 and PSN-1000(e) power supply boards provide power and communication expansion capability to the PFC-6000 series control panels. They provide an electrically isolated P-Link repeater output that supports additional power and communications distance.
PFC-6075 • 5403593 • Rev C • 2/13 Wiring Types Wiring specifications must be followed to prevent damage and/or other consequences. Table 22: PSN-1000/PSN-1000(E) Board Circuit Wiring Types Wiring Type Type of Circuit Voltage Power AC Connection High voltage Non-Power Limited...
PFC-6075 • 5403593 • Rev C • 2/13 Cabinet Installation The PSN-1000/PSN-1000(e) slides into the guides located at the bottom of the panel, and then secured with screws as shown in the following illustration. Figure 138. PSN-1000 Panel Installation Showing Cabinet...
PFC-6075 • 5403593 • Rev C • 2/13 Rechargeable Battery Circuit The battery charging circuit is on the power supply board providing terminal connections to connect the wire leads. The battery must be a recognized or listed sealed lead acid battery or equivalent. It is rated for 8 to 55 AH batteries and will operate the panel alarm for at least 24 hours and 5 minutes.
PFC-6075 • 5403593 • Rev C • 2/13 PSN-1000/PSN-1000(E) Battery Calculation Worksheet Complete one for all P-Link devices powered by the PSN-1000 / PSN-1000(E) Total Total Standby Alarm Device Type Standby Alarm (mA) (mA) (mA) (mA) PSN-1000 / PSN-1000(e) Main Board...
NAC circuits are power limited. • Type of NAC output is selectable, and may be configured for strobe synchronization with Potter/AMSeCO, Wheelock®, Gentex®, or System Sensor® strobe devices. Please refer to Potter document “5403592 NAC Compatibility Document” for this information.
Potter Part #3005013 Notes: The Potter part number for the listed end of line assembly is #3005013 eOL Resistor Assembly. The panel has ground fault detection on the input circuits. The impedance to ground for ground fault detection is 0 ohms.
PFC-6075 • 5403593 • Rev C • 2/13 Repeater Output The PSN-1000/PSN-1000(e) repeater output provides power which supports additional P-Link devices, including LCD Annunciators and/or SLC Loop expanders. This is possible because the P-Link repeater output reconditions and repeats all P-Link communications.
PFC-6075 • 5403593 • Rev C • 2/13 Municipal Box Connection When the PSN-1000/PSN-1000(e) is programmed as a municipal box connection, the circuit is power limited and supervised for open and short circuit conditions. It also provides a local energy connection. Please refer to the figure shown below for a wiring example.
PFC-6075 • 5403593 • Rev C • 2/13 PSN-1000/PSN-1000(E) Operations The PSN-1000/PSN-1000(e) operates as a fully integrated power expander. The input circuits and/or NAC circuits are configured in the same manner as any input circuit or NAC circuit in the system. Circuit functions and zone assignments are defined using the system software.
PFC-6075 • 5403593 • Rev C • 2/13 PSN-1000/PSN-1000(E) Programming The panel can be programmed to support up to thirty-one (31) PSN-1000/PSN-1000(e) Power expanders. each power supply provides six (6) NAC circuits (3A max), and two (2) dry contact input circuits. Both Class A and B configurations are supported;...
PFC-6075 • 5403593 • Rev C • 2/13 Notes: If a power supply is Class A, select the applicable NACs (NAC 1/2, NAC 3/4 or NAC 5/6). If a power supply is Class B, programming is completed. Class-A operation may be independently selected for the P-Link repeater output and any of the NAC circuit pairs.
PFC-6075 • 5403593 • Rev C • 2/13 Section 7: IP Communication The system's built-in, on-board IP Communicator provides notification to a remote monitoring company when alarms, troubles, and supervisory conditions occur. The IP Communicator is used with an IP capable Sur-Guard receiver by means of the Fibro protocol.
PFC-6075 • 5403593 • Rev C • 2/13 Programming the IP Communicator IP Reporting Accounts The "IP Reporting Accounts" section is used to program the IP Communicator operations and to customize the format of the reporting accounts. You may choose different settings for Alarms, Troubles and Supervisory conditions. Up to five (5) primary or secondary accounts may be configured.
Page 118
PFC-6075 • 5403593 • Rev C • 2/13 Figure 156. Example of Primary Account Settings "Expanded" Window Click here to collapse additional fields. Notes: – Use the scroll bar to display additional fields if not shown on right. – Click the collapse icon at any time to hide the account setting fields.
PFC-6075 • 5403593 • Rev C • 2/13 Appendix A: Basic Operating Instructions These instructions must be framed and displayed next to the PFC-6075 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72.
Page 120
PFC-6075 • 5403593 • Rev C • 2/13 Table 25: Operating Instructions Operation Task ENTER – Main Menu. •y Press •y Press 3 – Set Date / Time. Set Date / Time •y Use keypad to enter correct date; use right arrow to move through date field and to display time field.
PFC-6075 • 5403593 • Rev C • 2/13 Appendix B: Modem Connectivity Setup If your computer uses a modem for connectivity to the panel, choose the Options – Communications menu option. This involves choosing “Modem” as the transfer medium, and specifying the modem com port. In rare instances, a modem may also require an initialization string.
NFPA 72 to verify compliance with the applicable standards. Testing should be conducted by Potter factory trained fire alarm technician(s) in the presence of a representative of the Authority Having Jurisdiction (AHJ) and the building owners representative. Refer to NFPA 72 (National Fire Alarm Code), Inspection Testing and Maintenance.
PFC-6075 • 5403593 • Rev C • 2/13 Appendix D: PSN-1000/PSN-1000(E) Maintenance and Testing De-Energize Unit Prior to Servicing! The power supply board has one fuse on the board for the AC power over current protection. The AC fuse is rated at 8A 250vAC Time-Lag and screened onto the main board as F1.
PFC-6075 • 5403593 • Rev C • 2/13 Appendix F: Troubleshooting Tips This section provides basic error messages, their descriptions and recommended actions for each condition. Table 27: Troubleshooting Error Message Error Description/Action The panel is not able to communicate with the annunciator.
PFC-6075 • 5403593 • Rev C • 2/13 Appendix G: Control Panel Menu MAIN MENU 1=View History 3=Set Date/Time 4=Walk Test 2=Enable/Disable 2=By Zone 1=By Point Select Device Zone 1 Internal SLC 1=Disable Inputs Internal PWR 2=Disable Outputs MAIN MENU...
Page 127
Fire Panel Operating Instructions Normal Standby The green AC POWeR LeD will be illuminated and the user defined message on the LCD will be displayed. If the AC power is removed for more than 5 seconds, the green AC power LeD will extinguish. Acknowledging Off normal events are acknowledged by pressing the ACK key while reviewing events.