PFC-3002T Installation and Operation Manual Contents List of Figures.......................... ii Introduction ..........................1 Mechanical Installation ......................1 Function Selection ........................1 Wiring ............................2 Detection Zone........................2 Signal Zone .......................... 2 Alarm and Trouble Relays....................2 Remote Annunciation......................3 A.C. Power and Batteries..................... 3 Trouble Indicators and Controls....................
List of Figures List of Figures Figure 1: Backbox and flush trim mounting details ..............5 Figure 2: Circuit Board Layout ....................6 Figure 3: Detection and signal wiring..................7 Figure 4: Wiring table for detection zone ................... 8 Figure 5: Wiring table for bells and horns .................. 8 Figure 6: Alarm and trouble relay contacts and remote annunciation wiring instructions ..
PFC-3002T Installation and Operation Manual Introduction The PFC-3002T is a supervised two-zone 24VDC Fire Alarm Control Panel. The panel provides the following features: • Two Class B detection zones • One Class B signal zone, 1.7A • DIP switch selectable signal circuit outputs such as temporal or steady •...
Wiring DIP switch DSW1 is used to set the preferred signal zone 1 output, the signal silence inhibit, and the common trouble flash rate. The default output for the signal zone is temporal code. not used DIP switch DSW1 Signal Zone Trouble Buzzer and LED ON - steady ON - steady buzzer and LED...
PFC-3002T Installation and Operation Manual Remote Annunciation Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 on page 9 for wiring instruction. A.C. Power and Batteries The A.C. power is connected to the terminal block above the transformer.
Sequence of Operation Sequence of Operation Refer to Figure 2 on page 6 for the location of indicators and controls. Normal All indicators are normally OFF except for the green A.C. On LED. Alarm A red zone alarm LED will illuminate steadily for an incoming alarm. Signal Silence If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation.
Figure 2: Circuit Board Layout TRBL REMOTE ANNUNCIATION AUX. SIGNAL DETECTION ZONE ALARM RELAY TRL TRB A.C. RELAY BUZZER SIL. ZONE 1 SIL. A.C. ON ALARM TRBL. ZONE 1 TRBL. ZONE 2 SIL. TRBL. ALARM SIG. SIL. ZONE 2 BATT. SIG.1 RESET BATTERY...
PFC-3002T Installation and Operation Manual Figure 3: Detection and signal wiring Legend Heat Smoke Pull Station Bell Detector Detector Alarm threshold current is 21 mA. Maximum loop resistance is 100 ohms. Detection zone 1 22VDC 3mA STBY 3.9K 5mV ripple 1/2W 50 mA max.
Wiring Tables and Information Wiring Tables and Information Figure 4: Wiring table for detection zone Wire Gauge Maximum Wiring Run to Last Device (ELR) (AWG) 2990 4760 1450 7560 2300 12000 3600 19000 5800 30400 9200 Note: Maximum loop resistance should not exceed 100 ohms. Figure 5: Wiring table for bells and horns Signal circuit is rated for 1.7 amperes each.
Appendix A: Compatible Devices Appendix A: Compatible Devices Underwriter’s Laboratories Canada (ULC) Canadian 2-Wire Smoke Detector Control Panel Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 Make Model / Base Make Model / Base...
PFC-3002T Installation and Operation Manual Underwriter’s Labs Inc. (ULI) United States 2-Wire Smoke Detector Control Panel Compatibility Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same circuit, total standby current of all detectors must not exceed 3 •...
Page 16
Appendix A: Compatible Devices Smoke Compatibility Rated Smoke Detector Compatibility Detector Rated Standby Identifier Standby Make Model / Identifier Head / Make Model / Current Head / Base Current Base Base Base System Sensor (cont’d) Sentrol - ESL (cont’d) 732U / 702E, 2400 A - N/A 0.12 mA...
Power Requirements (All currents are in amperes) Total Model Number Description Standby Alarm Total Alarm Standby Fire Alarm, 2 Det, 1 PFC-3002T 0.076 0.135 Remote Trouble RTI-1 0.035 0.035 Indicator ♦ 2-Wire Smoke Detectors * 0.090...
Potter Electric Signal Co., manufactured equipment is guaranteed to be free of defects in material and workmanship for a period of one (1) year from the date of original shipment. Potter will repair or replace, at its option, any equipment which it determines to contain defective material or workmanship.