Potter PFC-3002T Installation And Operation Manual

Potter PFC-3002T Installation And Operation Manual

Fire alarm control panel

Advertisement

Quick Links

PFC-3002T
Fire Alarm Control Panel
INSTALLATION and OPERATION MANUAL
L NOTICE
All information, documentation, and specifications contained in this manual are subject
to change without prior notice by the manufacturer.
©2004 by Potter Electric Signal Company
November 2004
LT-514POT REV.0
firealarmresources.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PFC-3002T and is the answer not in the manual?

Questions and answers

Summary of Contents for Potter PFC-3002T

  • Page 1 Fire Alarm Control Panel INSTALLATION and OPERATION MANUAL L NOTICE All information, documentation, and specifications contained in this manual are subject to change without prior notice by the manufacturer. ©2004 by Potter Electric Signal Company November 2004 LT-514POT REV.0 firealarmresources.com...
  • Page 2 firealarmresources.com...
  • Page 3: Table Of Contents

    PFC-3002T Installation and Operation Manual Contents List of Figures.......................... ii Introduction ..........................1 Mechanical Installation ......................1 Function Selection ........................1 Wiring ............................2 Detection Zone........................2 Signal Zone .......................... 2 Alarm and Trouble Relays....................2 Remote Annunciation......................3 A.C. Power and Batteries..................... 3 Trouble Indicators and Controls....................
  • Page 4: List Of Figures

    List of Figures List of Figures Figure 1: Backbox and flush trim mounting details ..............5 Figure 2: Circuit Board Layout ....................6 Figure 3: Detection and signal wiring..................7 Figure 4: Wiring table for detection zone ................... 8 Figure 5: Wiring table for bells and horns .................. 8 Figure 6: Alarm and trouble relay contacts and remote annunciation wiring instructions ..
  • Page 5: Introduction

    PFC-3002T Installation and Operation Manual Introduction The PFC-3002T is a supervised two-zone 24VDC Fire Alarm Control Panel. The panel provides the following features: • Two Class B detection zones • One Class B signal zone, 1.7A • DIP switch selectable signal circuit outputs such as temporal or steady •...
  • Page 6: Wiring

    Wiring DIP switch DSW1 is used to set the preferred signal zone 1 output, the signal silence inhibit, and the common trouble flash rate. The default output for the signal zone is temporal code. not used DIP switch DSW1 Signal Zone Trouble Buzzer and LED ON - steady ON - steady buzzer and LED...
  • Page 7: Remote Annunciation

    PFC-3002T Installation and Operation Manual Remote Annunciation Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 on page 9 for wiring instruction. A.C. Power and Batteries The A.C. power is connected to the terminal block above the transformer.
  • Page 8: Sequence Of Operation

    Sequence of Operation Sequence of Operation Refer to Figure 2 on page 6 for the location of indicators and controls. Normal All indicators are normally OFF except for the green A.C. On LED. Alarm A red zone alarm LED will illuminate steadily for an incoming alarm. Signal Silence If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation.
  • Page 9: Figure 1: Backbox And Flush Trim Mounting Details

    Figure 1: Backbox and flush trim mounting details ” ” ” ” Optional flush mounting trim (model FA-102TR) ” ” ” dia. mounting hole ” firealarmresources.com...
  • Page 10: Figure 2: Circuit Board Layout

    Figure 2: Circuit Board Layout TRBL REMOTE ANNUNCIATION AUX. SIGNAL DETECTION ZONE ALARM RELAY TRL TRB A.C. RELAY BUZZER SIL. ZONE 1 SIL. A.C. ON ALARM TRBL. ZONE 1 TRBL. ZONE 2 SIL. TRBL. ALARM SIG. SIL. ZONE 2 BATT. SIG.1 RESET BATTERY...
  • Page 11: Figure 3: Detection And Signal Wiring

    PFC-3002T Installation and Operation Manual Figure 3: Detection and signal wiring Legend Heat Smoke Pull Station Bell Detector Detector Alarm threshold current is 21 mA. Maximum loop resistance is 100 ohms. Detection zone 1 22VDC 3mA STBY 3.9K 5mV ripple 1/2W 50 mA max.
  • Page 12: Wiring Tables And Information

    Wiring Tables and Information Wiring Tables and Information Figure 4: Wiring table for detection zone Wire Gauge Maximum Wiring Run to Last Device (ELR) (AWG) 2990 4760 1450 7560 2300 12000 3600 19000 5800 30400 9200 Note: Maximum loop resistance should not exceed 100 ohms. Figure 5: Wiring table for bells and horns Signal circuit is rated for 1.7 amperes each.
  • Page 13: Figure 6: Alarm And Trouble Relay Contacts And Remote Annunciation Wiring Instructions

    PFC-3002T Installation and Operation Manual Figure 6: Alarm and trouble relay contacts and remote annunciation wiring instructions N.O. Auxiliary common alarm relay contacts 28VDC, 3A (resistive) N.C. Cut JW3 for N.O. Common trouble relay contacts 28VDC, 3A Cut JW4 for N.C.
  • Page 14: Appendix A: Compatible Devices

    Appendix A: Compatible Devices Appendix A: Compatible Devices Underwriter’s Laboratories Canada (ULC) Canadian 2-Wire Smoke Detector Control Panel Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 Make Model / Base Make Model / Base...
  • Page 15: Underwriter's Labs Inc. (Uli) United States 2-Wire Smoke Detector

    PFC-3002T Installation and Operation Manual Underwriter’s Labs Inc. (ULI) United States 2-Wire Smoke Detector Control Panel Compatibility Notes: • Reset time, hold for five seconds minimum. • Whether mixing different models of compatible smoke detectors, or using the same model on the same circuit, total standby current of all detectors must not exceed 3 •...
  • Page 16 Appendix A: Compatible Devices Smoke Compatibility Rated Smoke Detector Compatibility Detector Rated Standby Identifier Standby Make Model / Identifier Head / Make Model / Current Head / Base Current Base Base Base System Sensor (cont’d) Sentrol - ESL (cont’d) 732U / 702E, 2400 A - N/A 0.12 mA...
  • Page 17: Underwriter's Labs Inc. (Uli) United States Signaling Device Control Panel Compatibility

    PFC-3002T Installation and Operation Manual Underwriter’s Labs Inc. (ULI) United States Signaling Device Control Panel Compatibility System Sensor - SpectrAlert P2415 P2415W P241575 P241575W P2475 P2475W P24110 P24110W S2415 S2415W S241575 S241575W S2475 S2475W S24110 S24110W H12/24 H12/24W MDLW Wheelock...
  • Page 18: Appendix B: Battery Calculations (Selection Guide)

    Power Requirements (All currents are in amperes) Total Model Number Description Standby Alarm Total Alarm Standby Fire Alarm, 2 Det, 1 PFC-3002T 0.076 0.135 Remote Trouble RTI-1 0.035 0.035 Indicator ♦ 2-Wire Smoke Detectors * 0.090...
  • Page 19: Warranty

    Potter Electric Signal Co., manufactured equipment is guaranteed to be free of defects in material and workmanship for a period of one (1) year from the date of original shipment. Potter will repair or replace, at its option, any equipment which it determines to contain defective material or workmanship.