Condensing Temperature Control (Cooling) - Sanyo SPW-T253GH56 Service Manual

Split system
Hide thumbs Also See for SPW-T253GH56:
Table of Contents

Advertisement

2-6 Condensing Temperature Control (Cooling)

Condensing temperature is controlled by the outdoor heat exchanger coil temperature as
sensed by sensor C2.
OUTDOOR UNIT
COIL TEMP. C2
OUTDOOR FAN
ELECTRONIC REF.
CONTROL VALVE
2
This chart shows how the outdoor fan speed and the electronic refrigerant control valve
react to coil temperature to control condensing temperature.
Sensor C2 is located in the middle of the outdoor unit heat exchange coil.
When C2 rises above 60°C the electronic refrigerant control valve opens at 50 steps/30
seconds, and the outdoor fan speed is forced to change to high (H) until C2 falls below
55°C.
60
(°C)
55
SPEED
H, M
Chart Explanations and notes
2. Processes and functions
FORCED
H, M
H
OPEN
– 32 –
0436_M_S
Fig. 9
SM830034