(4) LED Indication on the Outdoor Unit's P.C.B. Ass'y

If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Ass'y
light up to show the cause of the trouble, in addition to the Alarm message on the remote
controller.
LED 2 on
LED 1 on
Remote
P.C. board
P.C. board
controller
No message
E06, E07, L04
*
No message
P02
P04, P05
F04~F09
*
*
H01, H02
H04, H05
*
*
*
E15, E16
Flash at the same time
*
*
"SETTING"
Flash alternately
flashes.
NOTE
: LED lamps OFF
* REFRIGERANT SHORTAGE
Note particularly that a shortage of refrigerant is only shown by the outdoor P.C.B.
Ass'y LEDs and the Alarm Message does not appear on the Indoor Remote Controller .
The compressor keeps running even when the refrigerant is less, so when you find the
LED indication on the outdoor P.C.B. Ass'y, stop the air conditioner immediately to
avoid the compressor damage.
Possible cause of trouble
Normal
Outdoor unit serial communication signal is abnormal.
Outdoor unit address is duplicated.
Other outdoor units are performing auto address and
detecting refrigerant shortage.
FMo • CM thermal protection is in operation.
Power supply voltage is abnormal.
High voltage SW activates
Negative phase protector activates.
Sensor is abnormal. (Open or short)
Abnormal compressor current value is detected.
Scroll thermal protection failure is detected.
Auto address failure
Auto address is in operation.
: LED lamps ON (lights up) *: LED lamps ON (flashes)
LED 1
LED 2
– 65 –