CAPACITY CORRECTION FACTORS FOR VARIOUS
8
PIPE LENGTHS
1) COOLING CAPACITY
MODEL
25ft
40ft
1.0
0.992
PUG/H18
1.0
0.981
PUG/H24
1.0
0.981
PUG/H30
1.0
0.981
PUG/H36
PUG/H42
1.0
0.975
2) HEATING CAPACITY
Models
Less than 100ft
PUG/H18
1.00
1.00
PUG/H24
1.00
PUG/H30
1.00
PUG/H36
1.00
PUG/H42
Refrigerant piping length ( one way )
55ft
70ft
85ft
100ft
0.983
0.978
0.966
0.959
0.950
0.968
0.952
0.940
0.925
0.913
0.968
0.952
0.940
0.925
0.913
0.968
0.952
0.940
0.925
0.913
0.955
0.935
0.918
0.900
0.884
Refrigerant piping length (one way)
100~130ft
0.995
0.995
0.995
0.995
0.995
115ft
130ft
150ft
0.945
0.900
0.886
0.900
0.886
0.900
0.886
0.869
0.855
130~150ft
0.990
0.990
0.990
0.990
0.990