1.
CHEM FEED SET
Units with selectable feed timer(s) will have this SET
UP menu for selecting the chemical feed method and
setting the feed time. A selectable feed timer can be
programmed as one of the following:
1. PULSE TIMER - A timer activated by dry
contacts from a contacting head water meter
and includes an accumulator for counting the
number of pulse (contacts) before starting the
timer.
2. PERCENTAGE - A continuously repeating
timer where the cycle timer can be programmed
along with the percentage of ON time for the
cycle.
CHEM A PULSE TIMER
CHEM A PULSES
ENTER To change # of PULSES
CHEM A TIME XX.XX Min.Sec
ENTER To change Chem A time
Returns to CHEM FEED SET
XXX
-- CHEM FEED SET--
ENTER
Shows timer currently selected
ENTER To change to a different timer.
To cycle through timer options
ENTER To Select timer.
To bypass the feed method selection.
CHEM A PERCENTAGE
CHEM A PERCENT XXX
to change percentage
ENTER
CHEM A CYCLE XX.XX
To change Cycle Time
ENTER
Returns to CHEM FEED SET
8
CHEM A PULSE TIMER
CHEM A PERCENTAGE