9
ON
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
WAITING TIME
3. During the waiting time, the flue damper opens.
-
The icon
is activated.
-
The message FLUE DAMPER appears.
ON
Ê Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
FLUE DAMPER
4. After the flue damper opens, the text GLOW PLUG
appears on the display. This is followed by the
(pre-)glow of the hot surface igniter.
-
The icon
is dimmed.
-
The icon
is activated.
ON
Ê
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
GLOW PLUG
5. After a number of seconds pre-glow, the gas
control is opened and ignition takes place.
-
The icon
is activated.
-
The message IGNITION appears.
ON
Ê
Ê Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
IGNITION
6. After ignition, the flame is detected and the
appliance will be running. This means that actual
heating has started:
-
The icon
is dimmed.
-
The icon
is activated.
-
The message RUNNING appears.
ON
Ê
Ê
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
RUNNING
54
Starting and running
7. When the water reaches the set temperature, the
ON
13:45 Thursday
WAITING TIME
8. After the waiting time, the appliance enters an idle
ON
14:05 Thursday
demand ceases. The flue damper and gas control
both close and the burner tray is extinguished. A
new waiting time of about 10 seconds starts.
-
The icons
,
,
and
-
The icon
is activated.
-
The message WAITING TIME appears.
Ê Ê
65ÉC
Tset 65ÉC
state:
-
The icon
is dimmed.
-
The message WAITING TIME disappears.
-
With any subsequent heat demand, the
heating cycle will resume from step 1.
65ÉC