Allen-Bradley 1784-PCIC Installation Instructions Manual page 52

Series b controlnet universal pci communication interface card
Hide thumbs Also See for 1784-PCIC:
Table of Contents

Advertisement

7-2
Specifications
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Enclosure type rating
Power requirements
Power dissipation
Isolation voltage (continuous-voltage
withstand rating)
(1)
Wiring category
Certifications (when product is marked)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
(2)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication 1784-IN003D-EN-P - January 2006
IEC 61000-4-4:
± 2 kV at 5 kHz on communications ports
IEC 61000-4-5:
± 2 kV line-earth (CM) on communications ports
IEC 61000-4-6:
10Vrms with 1 kH sine-wave 80% AM from 150kHz...80MHz
None (open-style)
In US, this equipment must be powered from UL Listed Information
Technology Equipment or UL Listed Industrial Control Equipment. In Canada,
this equipment must be powered by an SELV source, CSA Certified
Information Technology Equipment, or CSA Certified Process Control
Equipment.
5V dc, 700 mA max., Class 2
3.5 W
50V continuous
Tested to withstand 600V for 60 s
2 - on communications ports
(2)
UR
UL Recognized Component Industrial Control Equipment
CSA CSA Accepted Component for Process Control Equipment
CSA Accepted Component for Process Control Equipment in Class
I, Division 2 Group A,B,C,D Hazardous Locations
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx (1784-PCIC only) European Union 94/9/EC ATEX Directive,
compliant with:
EN 50021; Potentially Explosive Atmospheres, Protection "n"
(Zone 2)
CI
ControlNet International conformance tested to ControlNet
specifications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1784-pcics

Table of Contents