9.
Preventative Maintenance
9.1
Preventive maintenance to be performed every two years.
In order to avoid problems due to accumulation of deposits, we suggest that you replace the centre metal tube,
the silicone drain tube and the low level sensor. We also suggest you replace the round o-ring gasket around
the tank. All these components are available in a kit.
9.2
To prepare for the Summer Season
Shut the main power OFF
Shut the water supply valve
Perform a complete maintenance as described in section 8
Dry the inside of the tank
Page 11
Need help?
Do you have a question about the ACU-STEAM and is the answer not in the manual?