electrical data / motor data
total unit amp draw
The total unit amp draw is a combination of the motor, the control step down transformer, and the power exhauster amp draw. The
control step down transformer includes damper actuators, ignition controllers, gas valves, control relays, amplifiers, and motor starters.
Motor Amp Draw (Tables 38.2 to 42.1)
table 38.1 - unit amps
control step down
digit 14
transformer amp draw
digit 15 - transformer
supply voltage
0 ➀
1
115/60/1
0
0.35
a
B
208/60/1
0
0.19
c
230/60/1
0
0.17
d
208/60/3
0
0.19
e
230/60/3
0
0.17
f
460/60/3 ➅
0
0.09
575/60/3 ➅
0
0.07
g
table 38.2 - motor data for digit 14 = a - 115v/60Hz/1Ph
digits
motor
17&18
size (HP)
type ➀
a1
1/3
a5
1/3
B1
1/2
B5
1/2
c1
3/4
c5
3/4
d1
1
d5
1
e1
1-1/2
e5
1-1/2
f1 or r1
2
f5 or r5
2
g1 or s1
3
g5 or s5
3
table 38.3 - motor data for digit 14 = B - 208v/60Hz/1Ph
digits
motor
17&18
size (HP)
type ➀
a1
1/3
B1
1/2
B5
1/2
c1
3/4
c5
3/4
d1
1
d5
1
e1
1-1/2
e5
1-1/2
f1 or r1
2
f5 or r5
2
H1 or t1
5
H5 or t5
5
38
Unit Amp Draw (Table 38.1)
Total Amp Draw
Power exhauster amp draw
2
3
4
75-175 200-400 500-800 840-960
0.65
1.3
2.17
1.4
0.36
0.72
1.2
0.7
0.33
0.65
1.09
0.6
0.36
0.72
1.2
0.7
0.33
0.65
1.09
0.6
0.16
0.33
0.54
0.30 ➁
0.13
0.26
0.43
0.24 ➁
motor
frame
size
ODP
56
TEFC
48
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
145T
TE
182T
ODP
184T
TEFC
184T
motor
frame
size
ODP
56
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
56
TEFC
56
ODP
145T
TE
182T
ODP
184T
TEFC
184T
=
=
+
=
model size
2.4
4.8
7.2
1.4
2.8
4.2
➀ Unit controls amp draw is included in master unit amp draw.
1.3
2.6
3.9
➁ Requires a 250 VA transformer.
1.4
2.8
4.2
➂ Requires a 500 VA transformer.
➃ Requires a 750 VA transformer.
1.3
2.6
3.9
➄ Requires a 1000 VA transformer.
0.65 ➂
1.3 ➃
2.0 ➄
➅ For Digits F (460V) and G (575V), amp draw shown is on
0.52 ➂
1.1 ➃
1.6 ➄
amp.
service
draw
factor
6.6
1.35
5.0
1.00
9.0
1.20
8.0
1.15
11.0
1.25
11.0
1.00
13.4
1.15
13.4
1.15
18.0
1.15
15.2
1.15
21.0
1.15
20.0
1.15
34.0
1.15
32.0
1.00
amp.
service
draw
factor
3.0
1.35
4.1
1.20
4.0
1.15
5.5
1.25
5.4
1.00
6.8
1.15
6.8
1.15
9.3
1.15
8.2
1.15
11.3
1.15
10.8
1.15
23.0
1.15
22.8
1.00
5-565.1
primary (line) side of required step-down transformer.
thermal
Weight
overload
(lbs)
Yes
25
Yes
25
Yes
23
Yes
28
Yes
25
Yes
30
Yes
32
Yes
37
Yes
40
Yes
45
No
49
No
54
No
81
No
83
thermal
Weight
overload
(lbs)
Yes
25
Yes
23
Yes
28
Yes
25
Yes
30
Yes
32
Yes
37
Yes
40
Yes
45
No
49
No
54
No
87
No
86
efficiency
➁ (%)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
efficiency
➁ (%)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Need help?
Do you have a question about the DBP and is the answer not in the manual?