TABLE 11
TEMPERATURE PRESSURE CHART
TEMP
(Deg. F)
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
101.6
65
111.3
70
121.4
75
132.2
80
143.7
85
155.7
90
168.4
95
181.8
100
196.0
105
210.8
110
226.4
115
242.8
120
260.0
125
278.1
130
297.0
135
316.7
140
337.4
145
359.1
150
381.7
24

15.5 SUBCOOLING CALCULATION

1. Measure the liquid pressure at the liquid line service valve.
R-22
2. Convert the liquid line pressure to saturated temperature. See Table 11.
PSIG
3. Measure the liquid line temperature at the liquid line service valve.
*29.4
4. Compare the liquid line temperature to the saturated temperature.
*29.1
5. The difference between saturated temperature and liquid line temperature is the
*28.5
subcooling. Subcooling normal range 9° to 12°.
*27.7
*26.6
*25.1
*23.0
*20.2
16.6
*11.9
*6.1
0.6
2.6
4.9
TABLE 12
7.5
HEAT PUMP SYSTEM TROUBLESHOOTING TIPS
10.2
13.2
16.5
SYSTEM PROBLEM
20.1
24.0
28.3
32.8
Liquid Restriction (Drier)
37.8
Low Evaporator Airflow
43.1
48.8
Low Outside Ambient Temperature
54.9
Inefficient Compressor
61.5
TEV Feeler Bulb Charge Lost
Poorly Insulated Sensing Bulb
68.5
76.1
84.1
92.6
HEAT PUMP SYSTEM
TROUBLESHOOTING TIPS
DISCHARGE
PRESSURE PRESSURE
Overcharge
High
Undercharge
Low
Low
Low
Dirty Heat Pump
High
Low
Low
Low
High
INDICATORS
SUCTION
SUPERHEAT SUBCOOLING
High
Low
High
Low
High
Low
Low
High
High
Low
Low
Low
High
Low
Low
Low
High
High
High
High
High
Low
High
High
High
Low
Low
COMPRESSOR
AMPS
High
Low
Low
Low
High
Low
Low
Low
High