Heat Controller HBH/V Compact Installation, Operation & Maintenance Manual page 29

Commercial horizontal & vertical packaged water-source heat pumps hbh & hbv compact horizontal & vertical hfc-410a units
Table of Contents

Advertisement

Heat Controller, Inc.
b) In cooling mode with compressor energized, FP1 is
greater than 125°F [52°C] for 30 continuous seconds,
or:
c) In cooling mode with compressor energized, FP2 is
less than 40°F [4.5°C] for 30 continuous seconds.
If a UPS condition occurs, the control will immediately
go to UPS warning. The status LED will remain on as
if the control is in normal mode. Outputs of the control,
excluding LED and alarm relay, will NOT be affected
by UPS. The UPS condition cannot occur during a
compressor off cycle. During UPS warning, the alarm
relay will cycle on and off. The cycle rate will be "on" for 5
seconds, "off" for 25 seconds, "on" for 5 seconds, "off" for
25 seconds, etc.
UPS warning code = 8
Swapped FP1/FP2 thermistors: During test mode, the
control monitors to see if the FP1 and FP2 thermistors
are in the appropriate places. If the control is in test
mode, the control will lockout with code 9 after 30
seconds if:
a) The compressor is on in the cooling mode and the
FP1 sensor is colder than the FP2 sensor, or:
b) The compressor is on in the heating mode and the
FP2 sensor is colder than the FP1 sensor.
Diagnostic Features
The LED on the CXM board advises the technician of the
current status of the CXM control. The LED can display
either the current CXM mode or the last fault in memory
if in test mode. If there is no fault in memory, the LED will
flash Code 1 (when in test mode).
HBH/V CompaCt
CXM Control Start-up Operation
The control will not operate until all inputs and safety
controls are checked for normal conditions. The
compressor will have a 5 minute anti-short cycle delay
at power-up. The first time after power-up that there is a
call for compressor, the compressor will follow a 5 to 80
second random start delay. After the random start delay
and anti-short cycle delay, the compressor relay will
be energized. On all subsequent compressor calls, the
random start delay is omitted.
IOM Instructions
CXM Controls

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents