Pre-Alignment Checklist - Honeywell FireLite BEAM355 Installation And Maintenance Instructions Manual

Single-ended reflected type projected beam smoke detector
Table of Contents

Advertisement

fiGuRE 6. wiRinG connEcTionS AT DETEcToR
T3
T2
fiGuRE 7. wiRinG DiAGRAM
T3
LISTED
+
REMOTE
POWER
SOURCE
+
* Only used for
BEAM355S. See
FROM PANEL OR
electrical ratings.
PREVIOUS DEVICE
F300-29-00
T1
T2
T1
+ –
+
COMMUNICATION LINE
TO NEXT
32 VDC MAX.
DEVICE
TWISTED PAIR IS
RECOMMENDED.
fiGuRE 8. wiRinG DiAGRAM (RTS451)
PIN 1
PIN 2
PIN 4
PIN 3
PIN 5
RTS451/KEY
fiGuRE 9. wiRinG DiAGRAM (RTS451)
SLC (+)
SLC (–)
C0260-01
Note 1: See electrical ratings section of this
inSTAllATion / AliGnMEnT
Reference Figures 10 through 14 for installation, alignment, and maintenance.
The alignment of the BEAM355/BEAM355S is divided into four steps: coarse
alignment, fine adjustment, final gain adjustment, and final verification. It is
necessary for all four steps to be executed properly to ensure proper alignment
of the product. If the detector and reflector are mounted per Mounting Loca-
tions and Mounting Instructions sections of this manual and the alignment
procedures are executed properly, false alarms and nuisance trouble signals
will be minimized.

PRE-AliGnMEnT chEckliST

Ensure that both the detector and reflector are mounted securely to
stable surfaces.
Ensure that all wiring is correct.
Ensure that terminal blocks are fully seated into their receptacles on
the detector.
Complete any wiring dressing to minimize movement to the detector
once the alignment procedure is completed.
Ensure that the appropriate number of reflectors are used for the in-
stalled distance. Distances between 230 and 328 Feet (70 – 100m) require
additional reflectors (4 total). The BEAMLRK accessory should be used
in these cases.
Ensure that the line of sight between the detector and reflector is clear
+
and that reflective objects are not too near. See Mounting Instructions
for more details.
Ensure that both the detector and reflector are mounted within their
C0337-01
operational parameters for off axis angles. See Mounting Instructions
for more details.
Disable the zone or system to prevent unwanted alarms before applying
power.
Ensure power to the detector is "ON".
Ensure that the appropriate address is set on the code wheels.
You are now ready to begin the alignment procedure.
5
DETECTOR
T1-1
POWER IN +
POWER OUT +
T1-2
POWER IN –
POWER OUT –
T2-1
REMOTE ALARM OUT
T2-2
AUX (–)
T2-4
RESET INPUT
T2-3
TEST INPUT
T3-3
REMOTE TROUBLE OUTPUT
OPTIONAL YELLOW LED
BEAM355S
Alarm
Signal
T2-1
Circuit
(Note 1)
T2-2
manual for circuit output ratings.
T1-3
T1-4
C0328-01
Red
C0329-00
I56-2425-007R

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Firelite beam355s