Download Print this page

Sensaphone 1104 Owner's Manual Addendum page 2

Hide thumbs Also See for 1104:

Advertisement

Sensaphone
®
Model 1104/1108 User's Manual
Model 1104/08 Owner's Manual Addendum
Sensaphone RemoteControl
How to use this Addendum
This is a supplement to the Sensaphone 1104/08 Owner's Manual.
Review the entire manual before reading this addendum. This
addendum does not explain the Sensaphone setup, configuration,
or operation. The purpose of this addendum is to instruct you on
the use of the remote control functions of your Sensaphone in
order to turn on or turn off devices such as any low-voltage
device, a high-voltage relay, or even an X10 device utilizing the
X10 Powerflash module, not included.
Sensaphone 1104/08 RemoteControl Feature
The Sensaphone 1104/08 RemoteControl allows you to monitor
and check on the status of your facility from any cellular or
ordinary telephone. The Sensaphone 1104/08 RemoteControl also
allows you to turn a device on or off using the 1104/08 keypad or
using your touch-tone telephone. You can also inquire about the
status of the device during a voice status report.
This Sensaphone contains a relay contact on the rear of the unit
(See Figure 1). The relay contact supports both a normally open
and a normally closed contact, commonly referred to as a "double
throw" relay.
When the Sensaphone relay is turned ON, a connection is made
between the ON and C (common) terminals and the connection to
the OFF terminal is disconnected. When the Sensaphone relay is
turned OFF, a connection is made between the OFF and the C
(common) terminals and the connection beetween the ON and C
(common) is disconnected (See Figure 1). When the Sensaphone
unit is put in standby mode, the relay remains in its last known
state. If the Sensaphone is completely shut down by removing the
batteries and unplugging it from power, the relay returns to an
OFF state, connecting the OFF terminal to the C (common).
The Sensaphone relay is a low voltage relay. Only voltages less
than 30 volts AC 2AMPS, or 30 volts DC 2 AMPS may be
switched. For higher voltages, an additional high-voltage relay
would be required.
A-1

Advertisement

loading

Related Products for Sensaphone 1104

This manual is also suitable for:

1108