5-4 Test Run

Perform the test run according to the test procedure of the test run check list.
(1) Test run of units by local remote controller
Perform the test run of the units by using the local remote controller or system controller.
1
* Confirm that all units are running normally.
(2) Test-operation of the indoor unit from LM ADAPTER
Turn on SW1-9 of LM ADAPTER.
1
* If there is even one indoor unit that is not running,the LM ADAPTER may not correctly recognize the indoor unit.
Refer to the next chapter " Troubleshooting ".
2
Finally turn OFF SW1-9, and verify that all indoor units are stopped.
(3) Test-operation of the indoor unit from L
If there is any tool which corresponds to L
the follwing procedure.
1
Set the LM ADAPTER in config .
If LM ADAPTER has been already bounded to another model (the service LED is not ON), don't apply any new binding.
2
During the test operation, use " nv1n Reguest ON/OFF " to verify that the indoor unit can be operated.
For details of " nv1n Reguest ON/OFF " , refer to the following.
nv1n Request ON/OFF command input
network input SNVT_switch nviOnOff_n;
This input network variable is used to allow On request or Off request of the indoor unit to be
changed via the network.
When the ventilator (LOSSNAY) Interlocks with the indoor unit, it becomes the same operation as
the indoor unit.
Valid range (SW1-7 OFF)
value field: not used
state field: 0
state field: 1
_n: ------------ Indoor unit address (M-NET)
* Refer to the index in the table below when performing update and poll (confirm state) of the
network variable for the L
3
Finally put the LM ADAPTER in the unconfig, and end the test operation.
Contact your dealer for details on trial operation from the L
®
W
ON
ORKS
W
ON
ORKS
= indoor unit or ventilator unit is " OFF "
= indoor unit or ventilator unit is " ON "
: Else = Indoor unit or ventilator unit is " OFF "
W
ON
ORKS
ON/OFF Reguest
index
nv name
1
nviOnOff_001
2
nviOnOff_002
:
:
49
nviOnOff_049
50
nviOnOff_050
®
,verify that it can be operated from L
®
tools (nodeutil etc.).
ON/OFF run state
index
nv name
51
nvoOnOff_001
52
nvoOnOff_002
:
:
99
nvoOnOff_049
100
nvoOnOff_050
®
W
network.
ON
ORKS
14
®
W
network according to
ON
ORKS