NOTE:1. All dimensions are from the surfaces of all tubes, combustion chambers, couplings, tees,
elbows and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from the burner.
3. "-" indicates an unapproved application. Roberts-Gordon does not allow the installation of
unapproved applications.
FIGURE 4
A
C
B
D
FIGURE 5
A
C
B
D
FIGURE 6
4
S
M
ERVICE
ANUAL
CLEARANCES TO COMBUSTIBLES
UNIVERSAL SHIELD (POSITION 1)
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
8
CRV-B-10
8
CRV-B-12
8
CRV-B-12A
8
UNIVERSAL SHIELD (POSITION 2)
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
4
CRV-B-10
4
CRV-B-12
4
CRV-B-12A
4
UNIVERSAL SHIELD (POSITION 3)
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
8
CRV-B-10
8
CRV-B-12
8
CRV-B-12A
8
(inches)
B
C
D
12
12
12
12
12
12
12
12
12
12
12
12
18
24
18
18
24
18
18
24
18
18
24
18
(inches)
B
C
D
20
48
20
20
48
20
20
48
20
20
48
20
36
48
36
36
48
36
36
48
36
36
48
36
(inches)
B
C
D
12
56
30
12
56
30
12
56
30
12
56
30
12
60
42
12
60
42
12
60
42
12
60
42
(centimeters)
A
B
C
10
30
30
30
10
30
30
30
10
30
30
30
10
30
30
30
20
45
60
45
20
45
60
45
20
45
60
45
20
45
60
45
(centimeters)
A
B
C
10
60
120
60
10
60
120
60
10
60
120
60
10
60
120
60
10
90
120
90
10
90
120
90
10
90
120
90
10
90
120
90
(centimeters)
A
B
C
10
30
140
75
10
30
140
75
10
30
140
75
10
30
140
75
20
30
150
105
20
30
150
105
20
30
150
105
20
30
150
105
D
D
D