Clearances To Combustibles - Roberts Gorden CoRayVac CRV-B-2 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRV-B-2:
Table of Contents

Advertisement

NOTE:1. All dimensions are from the surfaces of all tubes, combustion chambers, couplings, tees,
elbows and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from the burner.
3. "-" indicates an unapproved application. Roberts-Gordon does not allow the installation of
unapproved applications.
A
C
B
D
FIGURE 1
FIGURE 2
FIGURE 3

CLEARANCES TO COMBUSTIBLES

STANDARD REFLECTOR
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
4
CRV-B-10
4
CRV-B-12
4
CRV-B-12A
4
ONE SIDE REFLECTOR
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
4
CRV-B-10
4
CRV-B-12
4
CRV-B-12A
4
TWO SIDE REFLECTORS
Model
A
CRV-B-2
4
CRV-B-4
4
CRV-B-6
4
CRV-B-8
4
CRV-B-9
4
CRV-B-10
4
CRV-B-12
4
CRV-B-12A
4
(inches)
B
C
D
20
48
20
20
48
20
20
48
20
20
48
20
36
60
36
36
60
36
36
60
36
36
60
36
(inches)
B
C
D
12
56
20
12
56
20
12
56
20
12
56
20
12
60
42
12
60
42
12
60
42
12
60
42
(inches)
B
C
D
12
56
12
12
56
12
12
56
12
12
56
12
12
60
12
12
60
12
12
60
12
12
60
12
S
3: C
C
ECTION
RITICAL
ONSIDERATIONS
(centimeters)
A
B
C
D
10
50
120
50
10
50
120
50
10
50
120
50
10
50
120
50
10
90
150
90
10
90
150
90
10
90
150
90
10
90
150
90
(centimeters)
A
B
C
D
10
30
140
50
10
30
140
50
10
30
140
50
10
30
140
50
10
30
150
105
10
30
150
105
10
30
150
105
10
30
150
105
(centimeters)
A
B
C
D
10
30
140
30
10
30
140
30
10
30
140
30
10
30
140
30
10
30
150
30
10
30
150
30
10
30
150
30
10
30
150
30
3