Piping Length And Elevation - LG MFL39817319 Installation Manual

Air conditioner multi type
Table of Contents

Advertisement

Installation of Indoor, Outdoor Unit

Piping length and elevation

Multi Piping Type
Max total length
Outdoor Unit
of all pipes
Capacity
(A+B)/(A+B+C)/
(Btu/h class)
(A+B+C+D)
18k
50(164)
24k
75(246)
36k
75(246)
Indoor unit
Capacity
(Btu/h class)
9k
12k
18k
CAUTION: Capacity is based on standard length and maximum allowance
length is on the basis of reliability.
12 Multi Air Conditioner
Max length of
Min length of
each pipe
(A/B/C/D)
25(82)
25(82)
25(82)
Pipe Diameter
Unit : mm(inch)
Gas
9.52(3/8)
9.52(3/8)
12.7(1/2)
Max Elevation
between each
each pipe
indoor unit and
(A/B/C/D)
outdoor unit (h1)
3(10)
15(49)
3(10)
15(49)
3(10)
15(49)
Standard
Pipe Length
Unit : m(ft)
Liquid
6.35(1/4)
6.35(1/4)
6.35(1/4)
A
B
C
D
Max elevation
between indoor
units (h2)
7.5(25)
7.5(25)
7.5(25)
Additional
Refrigerant
Unit : g/m(oz/ft)
7.5(25)
20(0.22)
7.5(25)
20(0.22)
7.5(25)
20(0.22)
h2
Unit : m(ft)
Max.Combination
of Indoor unit
(Btu/h class)
24k
33k
48k
h1

Hide quick links:

Advertisement

Table of Contents
loading