GENERATOR
Model
Design
Frequency
Rated Output (COP)
Rated Voltage
Rated amperage
Phase & Wire
Power Factor
No. of Poles
Insulation
Voltage Regulation
Type of Coupling
DIESEL ENGINE
Model
Design
No. of cylinders
Bore × stroke
Displacement
Engine speed
Lubricating Oil
Oil capacity
Coolant capacity
SET
Fuel
Fuel consumption (at full load)
Fuel tank capacity
Continuous Operating Hours
Battery (V × Ah/5Hr)
Starting System
L × W × H
Approx Net Wt.
Terminal
Output
Receptacle
Emergency Stop System
GL9000
Unit
–STD
Salient-pole, revolving-field AC generator (AVR system with separate and self-excitation brush)
Hz
50
kVA
8
kW
8
V
220
A
36.4
ø-W
1-2
%
%
mm (in.)
L (cu. in.)
rpm
3000
L (U.S.gal.)
L (U.S.gal.)
L (U.S.gal.)/h
3.3 (0.87)
L (U.S.gal.)
hrs
8.5
mm (in.)
kg (lbs.)
In case of abnormal : Oil pressure, water temperature
–AUS
–USA
240
120/240
33.3
83.3/41.7
100
2
Rotor coil: Class F, Stator coil: Class B
5 (No load to full load)
Direct coupled
D722
Vertical, water-cooled, 4-cycle diesel engine
3
ø 67 × 68 (2.6 × 2.7)
0.719 (43.9)
API service class CD or higher
3.4 (0.90)
4.1 (1.1)
Diesel fuel No. 2 (ASTM D975)
28 (7.4)
55B24R (12V × 36Ah)
Electric
1281 × 618 × 698 (50.4 × 24.3 × 27.5)
295 (650)
SPECIFICATION
GL11000
–USA-TM
–STD
60
10
10
110/220
90.9/45.5
1-3
3600
4.1 (1.08)
7.0
3