Worcester 24ijunior Installation And Servicing Instructions page 38

Wall mounted combination boilers for central heating and mains fed domestic hot water
Table of Contents

Advertisement

No
Is the gas supply
connected and at the
correct pressure?
Yes
Remove front panel.
No
Reset and restart the
boiler. Can a flame be
seen through the spy
glass?
Yes
No
Is the boiler fully
water pressurised and
is all air vented?
Yes
No
Reset and restart the
boiler in CH mode.
Does the pump run?
Yes
Rectify gas supply
problem.
Remove inner cover.
No
Reset and restart the
boiler. Does a spark
occur across the
electrodes?
Yes
Turn off boiler. Remove
the multiway
connector from board
position ST16. Test
resistance across pins
1 and 2 (brown wires)
No
also pins 8 and 9
(violet).
Is resistance between
60Ω and 100Ω ?
Yes
Test resistance across
No
pins 4 and 5
(blue wires).
Is resistance between
10Ω and 25Ω ?
Yes
Is there continuity
No
between pins 6 and 7?
(orange wires to HL
stat)
Yes
Replace control board.
If problem not solved
replace gas valve.
Rectify fault.
Replace or repair
pump.
38
No
Are the electrodes and
gap and connections
in good order?
Yes
No
Test continuity of each
ignition cable.
Yes
Replace
control board.
Remove brown
connector from gas
No
valve.
Is there continuity
from brown and violet
connectors
to multiway
connector?
Yes
Replace gas valve.
Remove blue
connector from gas
No
valve. Is there
continuity from blue
wires to multiway
connector?
Yes
Replace gas valve
Replace overheat stat
or wiring to it.
Repair or replace
spark electrode
or HT leads
Replace (both) ignition
cables
Repair or replace
harness.
Repair or
replace
harness.