INSTALLATION
MANUAL
CONTENTS
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . 13
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . . . . 23
See the following page for a complete Table of Contents.
NOTES, CAUTIONS AND WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes are intended to
clarify or make the installation easier. Cautions are given to
prevent equipment damage. Warnings are given to alert
installer that personal injury and/or equipment damage may
result if installation procedure is not handled properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
SINGLE PACKAGED GAS/ELECTRIC
AIR COOLED AIR CONDITIONERS
3 THROUGH 5 NOMINAL TON
DYA: 036
048
042
060
SO 9001
Certified Quality
Management System
341426-BIM-A-0108

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 341426-BIM-A-0108 and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls 341426-BIM-A-0108

  • Page 1 CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT. SAVE THIS MANUAL SINGLE PACKAGED GAS/ELECTRIC AIR COOLED AIR CONDITIONERS 3 THROUGH 5 NOMINAL TON DYA: 036 SO 9001 Certified Quality Management System 341426-BIM-A-0108...
  • Page 2: Table Of Contents

    14 SUPERHEAT CHARGING TABLE FOR DYA042..20 15 SUPERHEAT CHARGING TABLE FOR DYA048..20 16 SUPERHEAT CHARGING TABLE FOR DYA060..20 341426-BIM-A-0108 LIST OF FIGURES Pg. # LIST OF TABLES Pg. # Johnson Controls Unitary Products...
  • Page 3: General

    B = 2nd Generation PRODUCT IDENTIFIER YA = 10 SEER Gas Heat/Electric FIGURE 1 - PRODUCT NOMENCLATURE Johnson Controls Unitary Products APPROVALS Design certified by CGA and AGA listed as follows: For use as a forced air furnace with cooling unit.
  • Page 4: Installation

    Units may also be moved or lifted with a fork-lift. Slotted openings in the skid are provided for this purpose. Forks must pass completely through the base. Refer to Table 2 for unit weights and to Figure 2 for approxi- mate center of gravity. 341426-BIM-A-0108 Johnson Controls Unitary Products...
  • Page 5: Clearances

    Secure with the four (4) screws used in step one. Seal duct covers with silicone caulk. Johnson Controls Unitary Products Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
  • Page 6: Thermostat

    Units are shipped with compressor mounting factory-adjusted for shipping. DISCONNECT THREE PHASE POWER SUPPLY Loosen compressor mounting bolts a half turn before operating unit. 341426-BIM-A-0108 NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS. 24 VOLT TRANSFORMER Johnson Controls Unitary Products...
  • Page 7: Natural Gas Application Data

    1,000 feet above sea level. Based on 2500 BTU/Ft. The air flow must be adjusted to obtain a temperature rise within the range shown. Continuous return air temperatures should not be below 55°F. Johnson Controls Unitary Products OUTPUT GAS RATE CAPACITY /HR.
  • Page 8: Gas Piping

    NOMINAL INCHES IRON PIPE SIZE LENGTH IN FEET 1/2” 3/4” Maximum capacity of pipe in thousands of BTU per hour (based upon a pressure drop of 0.5 inch water column). Johnson Controls Unitary Products 341426-BIM-A-0108 1” 1-1/4” 1,050 1” 1-1/4”...
  • Page 9: Flue Vent Hood

    1/2 psig (3.48 kPa). Johnson Controls Unitary Products FLUE VENT HOOD The flue vent hood with screen is not shipped attached. This hood must be installed to assure proper unit operation.
  • Page 10: Physical Data

    14.8 4 / 9 6 / 0 2.6/20x20 3.3/20x12 NPTI NPTI MAX. MAX. HACR UNIT FUSE TRANSFORMER BREAKER POWER SIZE, SIZE, FACTOR AMPS AMPS Johnson Controls Unitary Products 12 x 11 3,000 14.8 5 / 4 3.3/20x12 NPTI SIZE (VA)
  • Page 11: Unit Dimensions - Front

    41-1/2 Johnson Controls Unitary Products V E N T A I R O U T L E T H O O D...
  • Page 12: Unit Dimensions - Front & Bottom

    FIGURE 8 - UNIT DIMENSIONS - FRONT & BOTTOM FIGURE 9 - UNIT DIMENSIONS - BACK & BOTTOM 341426-BIM-A-0108 Johnson Controls Unitary Products...
  • Page 13: Sequence Of Operation

    If the pressure switch is lost during an ignition trial period, the control immediately de-energizes spark and gas. The control Johnson Controls Unitary Products begins pressure switch proving before an inter-purge and re- ignition attempt. PILOT FLAME STABILIZATION PERIOD...
  • Page 14: Post Purge

    It resets automatically. The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs, thus shut- ting down the ignition control and closing the main gas valve and energizing the blower. Johnson Controls Unitary Products 341426-BIM-A-0108...
  • Page 15: Cooling

    After a cool fan off delay timing of 30 seconds the circulating fan is de-energized. Johnson Controls Unitary Products CIRCULATING FAN When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fan to run at the cool speed.
  • Page 16: Post-Start Check List (Gas)

    MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT. The pilot flame should envelope 3/8 inch of the end of the flame sensor and not contain any yellow color, see Figure 12. 341426-BIM-A-0108 Line Pressure Johnson Controls Unitary Products...
  • Page 17: Adjustment Of Temperature Rise

    ------------------------------------------------------------------------- × 1.08 Degrees F Temp Rise Johnson Controls Unitary Products The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the rating plate and the data in Tables 3 and 4.
  • Page 18: Checking Supply Air Cfm

    After readings have been obtained, remove the tubes and reinstall the two ¼ inch plugs removed in Step 1. De-energize the compressors before taking any test mea- surements to ensure a dry indoor coil. 341426-BIM-A-0108 Johnson Controls Unitary Products...
  • Page 19: Dya Coil Delta P Vs Airflow

    28.4 23.3 24.8 19.5 21.1 15.7 17.5 11.9 13.8 10.6 Johnson Controls Unitary Products DYA Coil Delta P vs Airflow DYA042 1000 1200 1400 1600 Airflow (CFM) SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM INDOOR WB TEMP. (°F) 29.7...
  • Page 20: Superheat Charging Table For Dya042

    17.1 19.1 21.1 11.9 14.5 17.1 19.7 10.0 12.9 15.8 18.7 11.3 14.5 17.7 13.2 16.7 11.8 15.7 Johnson Controls Unitary Products 32.4 31.1 29.9 28.6 27.3 25.9 24.5 22.4 20.3 18.1 16.0 31.0 29.6 28.2 26.8 25.4 24.4 23.3 22.3...
  • Page 21: Typical Wiring Diagram Dya 036, 042, 048, 060 (208/230-3-60 Power Supply)

    341426-BIM-A-0108 FIGURE 14 - TYPICAL WIRING DIAGRAM DYA 036, 042, 048, 060 (208/230-3-60 POWER SUPPLY) Johnson Controls Unitary Products...
  • Page 22: Typical Wiring Diagram Dya 036, 042, 048, 060 (460-3-60 Power Supply)

    341426-BIM-A-0108 FIGURE 15 - TYPICAL WIRING DIAGRAM DYA 036, 042, 048, 060 (460-3-60 POWER SUPPLY) Johnson Controls Unitary Products...
  • Page 23: Low Speed

    See unit nameplate for maximum fuse size and/or circuit breaker size and minimum circuit ampacity. If both LR and ASCT are present, wire 801/BL and 805/ BL are connected to ASCT-3. If only LR is present wire Johnson Controls Unitary Products MED SPEED BLK (HI) BLK / WHT...
  • Page 24: Typical Wiring Diagram Legend

    IDFAN ODFAN RC1 / RC2 FIGURE 17 - TYPICAL WIRING DIAGRAM LEGEND Subject to change without notice. Printed in U.S.A. Copyright © 2008 by Johnson Controls, Inc. All rights reserved. LEGEND AUXILARY LIMIT SWITCH ANTI-SHORT CYCLE TIMER (OPTIONAL) BLOWER RELAY...