Ignition Delay; Adjusting The 3.6.6. Soft Lighta; Changing Thet - Ariston Type C Installation And Servicing Instructions

Aco series
Table of Contents

Advertisement

3.6.4 I
D
A
GNITION
ELAY
DJUSTMENT
3.6.5 A
M
DJUSTING THE
AXIMUM
3.6.6 S
L
A
OFT
IGHT
DJUSTMENT
3.7 C
HANGING THE TYPE OF GAS
H
P
EATING
OWER
The ignition delay can be adjusted to between 0 and 7 minutes.
The delay is factory set to 2 minutes.
The value set can be displayed and modified as illustrated in
paragraph 3.6.1 (parameter 3).
The maximum heating power can be adjusted to between the
maximum power allowed by the boiler (24 kW) and the minimum
one (8 kW). The value is factory set to 70% of the maximum
power.
The value set (expressed as a percentage) can be displayed
and modified as illustrated in paragraph 3.6.1(parameter 2).
The soft light can be adjusted between the maximum power
(shown on the display as "00", i.e. 100%) and minimum power
(shown on the display as "01", i.e. 1%). The boiler is factory set
to a value which is suitable for ignition with any type of gas
(approx. 33%).
The value set (expressed as a percentage) can be displayed
and modified as illustrated in paragraph 3.6.1 (parameter 1).
Initially the ACO boiler is only available for use with
methane Gas (G20).
35