Viessmann VITODENS 200-W Installation Instructions Manual page 69

4.8 to 35.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Vitoden 200-W pages 44 -
Function sequence and possible faults
Burner in operation
Automatic
calibration of the
combustion control
unit
For further details regarding faults see the service instructions.
4/9/07
7:56 pm
Yes
No
Stops below the
set boiler water
temperature and
restarts immediately
Yes
No
Fault Eb
Page 26
(cont.)
Check the flue gas
system for
soundness (flue
gas recirculation),
check the gas flow
pressure
Check the
connecting cable
and the ionisation
electrode. Check
the flue gas
system (flue gas
recirculation)
69