Nortec Gas-fired Humidifier Installation, User & Maintenance Manual page 25

Gas-fired humidifier
Table of Contents

Advertisement

The table below lists the outlet pressure of the gas
valve under different conditions. This table should be
used as a guide when servicing/troubleshooting the
unit. The actual measured manifold pressure should
fall within the range shown.
Maximum Vent
Minimum Vent
Length
length
(70 ft. 21m)
Maximum firing
-0.62" W.c.
-0.40" W.c.
rate
Minimum firing
-0.25" W.c.
-0.15" w.c.
rate
..
-~
...
/
- 22-