INSTALLATION INSTRUCTIONS
Indoor unit installation(wall-mounted type)
1. Fit the Installation Plate
1 . F it th e i nstal l a t i o n p late ho r izontally
o n s tructural p a rts of t h e wal l w ith
s p a c e s a round t h e ins t a l l a t i o n plat e .
2 . I f th e w all is m ade of b rick, co n c rete
o r t he li k e , d rill fi v e o r ei g h t 5 mm dia m e t e r
h o l e s i n th e w all.Ins e r t C lip an c h o r f or
a p p r o p r iate mo u n t i n g s crew s .
3 . F it th e i nstal l a t i o n p late on t he wa l l
w i t h f ive or e ight typ e ? A ? scr e w s .
Note:
Fit the Installation Plate and drill
holes in the wall according to the
wall structure and corresponding
mounting points on the installation
plate. The Installation Plate may be
slightly different according to the
different models of indoor unit.
(Dimensio n s a re in ? m m? un l e s s
ot h erwise st a t e d )
2. Drill a hole in the wall
1. Determine hole positions according
to the diagramdetailed in Fig.5. Drill
one (1) hole (φ65mm) slanting slightly
to outdoor side.
2. Always use wall hole conduit when
drilling metal grid, metal plate or the like.
3. Connective Pipe and Drainage
Installation
Drainage
1. Run the drain hose sloping downward.
Do not install the drain hose as
illustrated in Fig.7.
Correct orientation
of Installation Plate
Fig.4
150mm or more to ceiling
C
Indoor unit outline
Installation plate
120mm or
more to wall
Left rear side
refrigerant
pipe hole φ65
Model A (A: 710, B: 250, C:100, D: 110)
Model B(
A: 790, B:265, C:100, D: 150
Model A (A: 710, B: 250, C:100, D: 110)
Model B(
A: 790, B:275, C:100, D: 85
Model C(
A: 850, B:290, C:100, D: 115
150mm or more to ceiling
Installation plate
Indoor unit outline
150
120mm or
more to wall
Left rear side
refrigerant
pipe hole φ65
Model A (A: 920, B: 293, C:150, D: 185)
Model B(
A: 995, B:293, C:150, D:200
Model C(
A: 850, B:305, C:150, D:145
Indoor
Do not block water flow by a rise.
6
D
120mm or
more to wall
Right rear side
refrigerant
pipe hole φ65
A
)
)
)
190
120mm or
more to wall
Right rear side
refrigerant
pipe hole φ65
918
)
)
Fig.5
Wall
Outdoor
Fig.6
Do not put the end of
drain hose into water.
Fig.7