INSTALLATION INSTRUCTIONS FOR THE
LIEBERT LM SERIES SURGE PROTECTIVE DEVICE
The Liebert LM Series Surge Protective Device is a high
quality, high energy surge current diversion system designed
to protect sensitive equipment from damaging transient
voltage surges. Proper installation is required for maximum
system performance.

Unpacking and Preliminary Inspection

Inspect the shipping crate(s) for damage or signs of
1.
mishandling before unpacking the unit.
Remove any securing bands and cardboard packing
2.
and inspect the unit for any obvious shipping damages.
If any damage as a result of shipping is observed,
3.
immediately file a claim with the shipping agency and
forward
a
copy
to
Representative.

Handling Considerations

Larger units are bolted to a shipping pallet to facilitate
handling by forklift or pallet jack.
weight. Refer to the cabinet data furnished with the unit.
Typical size and weights are referred to in Figure 1.

Storage

The unit should be stored in a clean, dry environment.
Storage temperature range is -55ºC (-67ºF) to +85ºC
(+185ºF). Care should be taken to avoid condensation. All
packing and shipping materials should be left intact until the
unit is ready for final installation. If the unit has been stored
for an extended period of time, the unit should be cleaned
and carefully inspected before placing into service.

Location Considerations

Environment – The unit is designed for operation indoors in
ambient temperatures of -40ºC (-40ºF) to +60ºC
(+140ºF) with a relative humidity of 0% to 95% (non-
condensing).
The unit is provided in a metallic industrial enclosure,
which should not be installed in areas with excessive
dust, corrosive vapors, flammable materials or explosive
atmospheres.
Installation, Operation
and Maintenance Manual
®

UNPACKING AND INSTALLATION

your
local
Liebert
Sales
Check the size and
The installer should perform the following steps to assure a
quality installation. The entire installation manual should be
read before starting installation. These instructions do not
replace national or local electrical codes. Check applicable
electrical codes to ensure compliance. Installation of the
Liebert LM Series Surge Protective Device should only be
performed by qualified personnel.
Audible Noise – The audible noise of the unit is less that 40
dBA at 5 feet, which allows its placement within almost
any room if desired.
Service Clearances – Service clearance is needed only at the
front of the unit. Thirty-six inches (36in / 914mm)
minimum is recommended.
Equipment
Performance
performance, the unit must be located as close to the
protected circuit as practical to minimize interconnecting
wiring length.
For optimum transient surge protection, coordinated
surge suppression should be applied at the service
entrance and all other electrical connections to the
building (telephone, CATV, etc.), at known surge
generating loads within the building (large motors, arc
welders, switched capacitors, etc.), as well as at sensitive
electronic
loads
(such
appliances, solid state motor drives, etc.).
interconnected electronic loads (such as by way of data
cabling), transient surge suppression should also be
applied to the interconnecting wiring (data cables).
Mounting – Unit is intended to be wall mounted. Refer to
Figure 1 or unit submittal drawings for typical mounting
dimensions and weight.

Door Closing Adjustments

Single Door (Wall Mounted) – If the surface on which the
enclosure is mounted is not flat, the door may not open
and close properly.
mounted on a large door, the door may sag slightly. If
the top of the door strikes the lip which extends around
the body opening, place metal shims behind the
mounting foot which is located at the bottom of the
enclosure and closest to the door hinge. Place the shims
between the mounting foot and the wall or mounting
surface.
Be sure all mounting screws are tightened
securely.
- 2 -
Surge
Suppression
Systems
For
maximum
system
as
computers,
electronic
Also, if heavy equipment is
LM Series
Rev 0, 5/99