Q7055B1047 OPEN VIEW NET SERVER (OVN)

SPECIFICATIONS

Models: Q7055B1047 Open View Net Server (OVN).
Electrical Ratings:
Supply Voltage: 24 Vac, 50 to 60 Hz, 24 Vdc
(external power supply required).
Power Consumption: 8 VA.
Temperature Ratings:
Operating: 32° F to 120° F (0° C to 49° C).
Storage: -13° F to +185° F (-25° C to +85° C).
Humidity Ratings: 5 to 93% RH, non-condensing.
System Data:
Processor: AMD SC2200, 266 MHz, 32 bit microprocessor.
Data Transfer: 10/100 Mbit/sec., 802.3 Ethernet.
LAN Interface: 10/100BaseT (RJ-45).
Field Bus: RS-485 DC coupled XL5000 C Bus.
Device Interface: Serial RS-232.
Memory: SODIMM, Compact Flash.
OVN supports a maximum of 2,000 points
(access/subscription).
MTBF: 100,000 hours.
Safety:
Protection Standard: IP20 according to EN60529.
Protection Class: II according to EN60730-1.
Flame Retardant: V0 according to UL 94.
Dimensions (W x H x D): 2-13/16 in. (72 mm) x 8-13/16 in.
(224 mm) x 7-13/16 in. (199 mm).
Weight: 3.0 lb (1.4 kg).
Approvals:
Electromagnetic Compatibility (EMC): EN50081-1 and
EN50082-2.
Electromagnetic Emission (EME): FCC Class A.
Energy Management: UL 916 (pending).
Additional Equipment:
DC Power Supply: Jameco
0.500 mA output, wall mounted power cube, Class 2.
AC Power Supply: 120 Vac/50 to 60 Hz input, 24 Vac
output,14507287 series, or 14507350-002, listed.
Mounting: 14006090-555151 series communication panels.
50013930-001 Mounting Bracket

BEFORE INSTALLATION

Perform the following steps prior to installing the OVN server:
1. Verify that the product has been received without
damage.
2. Verify that the correct OVN server has been delivered.
3. Check the package contents. The following items are
included in each product package:
• Building Network Adapter device.
• Building Network Adapter driver software CD.
• Building Network Adapter Installation Instructions.
• Bag of installation materials as follows: one
3-pole Phoenix power connector, two 2-pole Phoenix
controller bus channel connectors, four optional wall
mounting clips, four small inserts and four screws.
95-7711
®
Model No. DDU240050, 24 Vdc,
4. Read the CONNECTIONS section carefully prior to
connecting power and data interface cables to the OVN.
5. Refer to the INSTALLATION INSTRUCTIONS for each
component connected to the OVN:
• Form no. 95-7481, Excel 100, 500, 600 Series.
Controller Subpanel Installation Instructions.
• Form no. 95-7524, Excel 500/600 Control System
Installation Instructions.
• Form no. 95-7705, EBI™ LAN Interface Installation
Instructions.
WIRING
CAUTION
Shock Hazard.
Removal of the OVN cover can result in electrical
shock.
Do not remove cover. There are no user serviceable
parts inside.

Location and Mounting

The OVN server can be mounted in several ways; as a single
server or wall/cabinet mounted.

Single Server

Fig. 2 shows the single OVN server operating position; for
example, on a desk.
Fig. 2. Single server operating position.
2
EX CE L
TM
50 00
OP EN VIE W
NE T
Re se t
Po we r
Bo ot
NM L
Rx
Tx
10
10 0
AC T
M25117

Advertisement

Table of Contents
loading

Table of Contents