9.5.9.
Energy Save Control
• During Cooling Operation, press "Economy" button at remote control to enable Energy Saving Operation
• The air conditioner judges the stable condition, where the different between indoor suction temperature and setting temperature
is 1°C for 30 minutes and moderately shifts the set temperature in 0.5°C steps (Maximum 2°C) to control energy saving opera-
tion.
• If temperature different is out of range, energy save operation will not start.
• Energy Save Operation is canceled by pressing the "Economy" button again.
9.6.

Test Run (Forced Cooling mode)

• Test run is necessary after installation is completed.
• To enable test run operation, at outdoor PCB, set the DS1 Switch 1 to ON position.
• Press Test Run button for 1 second.
9.6.1.
Valve Error
• During test run, if the 3-way valve is close, valve error is shown on wired remote control.
• This control is to protect the compressor.
• Valve error is detected if comply with conditions below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes).
- Indoor heat exchanger temperature at compressor start - 3ºC < current indoor heat exchanger temperature for 1 minutes.
- Indoor suction temperature - 3ºC < current heat exchanger temperature for 5 minutes.
Energy save control time chart
34