Operation Range - Panasonic CS-D34DTQ Service Manual

Hide thumbs Also See for CS-D34DTQ:
Table of Contents

Advertisement

1.4.

Operation range

1.4.1.
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be bal-
anced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
MODEL
CU-
D34DBQ7
D43DBQ7
D50DBQ7
1.4.2.
Indoor and Outdoor Temperature
• Model 50Hz / 60Hz CU-D34DBQ7 CU-D43DBQ7 CU-D50DBQ7
Operating
Cooling
Unit Main Power
Phase, Volts
3 ~ 220
3 ~ 220
3 ~ 220
Hz
Indoor Temp. (D.B./W.B.) (°C)
Max.
50/60
32/23
Hz
50/60
50/60
50/60
Min.
21/15
4
Applicable Voltage
Max.
242
242
242
Outdoor Temp. (D.B./W.B.) (°C)
Max.
43/-
Min.
198
198
198
Min.
5/-