1.4.
Operation range
1.4.1.
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be bal-
anced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
MODEL
CU-
D34DBQ7
D43DBQ7
D50DBQ7
1.4.2.
Indoor and Outdoor Temperature
• Model 50Hz / 60Hz CU-D34DBQ7 CU-D43DBQ7 CU-D50DBQ7
Operating
Cooling
Unit Main Power
Phase, Volts
3 ~ 220
3 ~ 220
3 ~ 220
Hz
Indoor Temp. (D.B./W.B.) (°C)
Max.
50/60
32/23
Hz
50/60
50/60
50/60
Min.
21/15
4
Applicable Voltage
Max.
242
242
242
Outdoor Temp. (D.B./W.B.) (°C)
Max.
43/-
Min.
198
198
198
Min.
5/-