Compact gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for VITODENS 333:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Fault code
Const.
in the dis-
play
dd
dE
E4
X
E5
X
E6
X
F0
X
F1
X
80
Weat-
System
h.
character-
comp.
istics
X
X
X
Burner
blocked
X
Burner
blocked
X
Burner in
fault state
X
Burner
blocked
X
Burner in
fault state
(cont.)
Cause
Remedy
Room temperature
Check the
sensor heating cir-
room tem-
cuit A1 lead break
perature sen-
sor - heating
circuit A1
Heating circuit M2
Check the
room temperature
room tem-
sensor lead break
perature sen-
sor - heating
circuit M2
Fault - supply vol-
Replace con-
tage
trol unit
Internal error
Check the
ionisation
electrode and
leads. Check
flue gas sys-
tem for
soundness.
Press E.
Flue gas/air supply
Check the
system blocked
flue gas/air
supply sys-
tem. Check
the differen-
tial pressure
sensor.
Press E.
Internal error
Replace con-
trol unit
Flue gas tempera-
Check the
ture limiter has
heating sys-
responded
tem water
level. Vent
the heating
system.
Press reset
E no sooner
than after
20 minutes.