16 TW Series / Water to Water

CHIller Mode

Table 1 - r410a units - full load
Cooling Mode operating pressures (pSIG)
Entering Fluid
Temp °F
65
55
45

boIler Mode

Table 2 - r410a units - full load
Heating Mode operating pressures (pSIG)
Entering Load
Deg °F
70
90
110
v
N OTE: Ratings are based on water flow rates stated in specification sheets. 2.4 GPM/ton on evaporator
side and 10°F ∆ T on condensor side when in the chiller mode. Boiler mode conditions are 2.4 GPM/ton on
the source side and 10°F ∆ T on load side. The values are typical and may vary between models.
6 720 220 047
Entering Source Condenser Temperature °F
75 °F
Suction
Discharge
Pressure
Pressure
99-116
290-320
91-107
265-311
76-91
265-311
Entering Source
Suction Pressure
40
60
99-116
80
130-145
40
60
99-116
80
130-165
40
60
99-116
80
139-165
Subject to change without prior notice
85 °F
Discharge
Suction Pressure
Pressure
107-123
325-358
91-107
303-350
76-91
295-345
Discharge Pressure
68-83
255-290
270-305
290-325
76-91
350-380
358-390
370-400
76-91
455-480
470-500
480-575

operating pressures

95 °F
Discharge
Suction Pressure
Pressure
107-123
370-400
99-116
370-400
83-99
358-390
Revised 03-11