Dunkirk Q95M-200 Installation, Operation & Maintanance Manual page 21

Gas-fired direct vent modulating hot water boiler
Table of Contents

Advertisement

Antifreeze solutions can breakdown over time. Failure to
check antifreeze chemistry, including inhibitors, annually
may result in accelerated corrosion of boiler and other
system components. Consult with the antifreeze manufac-
turer for recommendations.
Use of antifreeze in any boiler will reduce heating capacity
as much as 10-20%. This must be taken into consideration
when sizing the heating system, pumps and expansion
tank. Consult antifreeze manufacturer's literature for spe-
cific information on reduced capacity.
Recommended Aluminum Antifreeze
& Inhibitor Suppliers
Interstate Chemical
2797 Freedland Road
P.O. Box 1600 Hermitage, PA 16148-0600
www.interstatechemical.com
Tel: 800-422-2436 Fax: 724-981-8383
Noble Company
PO Box 350 Grand Haven, MI 49417
www.noblecompany.com
Tel: 800-878-5788 Fax: 800-272-1519
Rhomar Water Management, Inc.
PO Box 229 Springfield, MO 65801
www.rhomarwater.com
Tel: 800-543-5975 Fax: 417-862-6410
* These products may be used to adjust the pH level of the hydronic system, but on occasion may not resolve the pH issue. In these cases it is recommended
to flush the system and refill with untreated water and new boiler manufacturer approved antifreeze suitable for Aluminum heat exchangers.
IMPORTANT
: Regardless of antifreeze or inhibitors used, be sure to follow the antifreeze manufacturer's instructions for use, safe handling and storage of
their products. Refer to the MSDS (Material Safety Data Sheets) provided by the antifreeze manufacturer for potential hazards and first aid procedures for
exposure or ingestion.
Antifreeze Testing Services:
and contractor. Contact the antifreeze manufacturer regarding their sampling plan procedure. Consult the antifreeze manufacturer for details on sample
requirements and recommendations.
The boiler manufacturer reserves the right to make changes without notice.
Xii - water treatment & freeze protection
NOTICE
Each of the recommended antifreeze manufacturers have developed a sampling program available to the homeowner
Using the antifreeze manufacturer's instructions to deter-
mine the freezing temperature needed and use the correct
amount of antifreeze. Never exceed 50% antifreeze by
volume.
The boiler operating pressure must remain below 15 psi
for antifreeze solutions that specify a maximum of 250˚F
(121˚C).
Recommended Products
Intercool NFP-30,40,50 AA
Intercool RPH-15*
Noburst AL Antifreeze
Rhogard Antifreeze
Pro-Tek 922 Inhibitor*
21