Boiler Plumbing Instructions

1. Read the Axeman Anderson boiler manual, Becket Oil Gun Manual (or Carlin Gas Gun Manual), the
Honeywell L7224C manual found in the envelope that is shipped in the ash pan.
2. Connect all plumbing in accordance with local codes and requirements.
ADDITIONAL INFORMATION ON BOILER CONNECTIONS:
3. Since the WL110 has a water capacity of 12 gallons, it is important that the plumbing connection
method controls the return temperature to ensure a boiler differential temperature of around 25*F. This
can be accomplished by using a primary/secondary connection or by running the circulator continuously
to maintain the temperature of the heating loops.
NOTE: IT IS IMPORTANT FOR THE DUMP ZONE TO BE CONNECTED AND FUNCTIONAL BEFORE LIGHTING
THE BOILER TO PREVENT AN OVERTEMP CONDITION.

Boiler Pre-Operation Instruction

1. Refer to Appendix B for converting unit from oil to coal operation and vice versa.
2. Read the Axeman Anderson boiler manual, Becket Oil Gun Manual (or Carlin Gas Gun Manual), the
Honeywell L7224C manuals AGAIN!
3. Verify that all piping has been pressure tested and that the cold water supply is turned on and the fill
valve is operating properly (there should be around 12 PSI registering on the Tridicator located on the
DHW coil.
4. Verify that all control wiring has been installed and verify that the thermostat (s) is hooked up to the
L7224 triple aquastat.
5. Verify that the L6006 high limit aquastat terminals R to B are in series with the power feeding the
boiler, verify that terminals R to W are feeding the dump zone circulator pump.
DANGER - Risk of Fire or Explosion - Do not burn garbage, gasoline, drain oil or other flammable liquids.
CAUTION – HOT SURFACES – KEEP CHILDREN AWAY – DO NOT TOUCH APPLIANCE DURING OPERATION
DO NOT CONNECT THIS UNIT TO A CHIMNEY SERVING ANOTHER APPLIANCE
WARNING –
RISK OF FIRE – DO NOT OPERATE WITH A FLUE DRAFT EXCEEDING -.07" wc,
OPERATING AT A DRAFT ABOVE -.07" wc CAN CAUSE UNIT TO BURN BACK INTO THE HOPPER
DO NOT OPERATE WITH ASH REMOVAL DOOR OPEN
DO NOT STORE FUEL OR OTHER COMBUSTIBLE MATERIAL WITHIN MARKED INSTALLATION CLEARANCES
CAUTION – BURN RICE OR BUCKWHEAT SIZED ANTHRACITE COAL ONLY
PLEASE SAVE THESE INSTRUCTIONS