Vermont Castings RFSDV24 Installation Instructions And Homeowner's Manual page 15

Freestanding direct vent fireplace
Hide thumbs Also See for RFSDV24:
Table of Contents

Advertisement

7. Install roof support (Fig. 22) and roof flashing making
sure upper flange of flashing is below the shingles.
(Fig. 25)
8. Install appropriate pipe sections until the venting is
above the flashing. (Fig. 25)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.
23)
11. Apply high temperature sealant to 4" and 7" collars.
Attic Insulation
Shield
11"
Ceiling In-
stallation
Fig. 24 Place firestop spacer(s) and secure.
10003550
11"
Joist
11" x 11" (295 x 295 mm)
Upper Floor
Joist
Firestop Spacer
Nails (4)
FP1516
RFSDV24/34 Freestanding Direct Vent Gas Fireplace
If there is a room above ceiling level,
firestop spacer must be installed on both
the bottom and the top side of the ceiling
joists. If an attic is above ceiling level a
7DVAIS (Attic Insulation Shield) must be
installed.
The enlarged ends of the vent section
always face downward. (Fig. 25)
Fig. 25 Roof flashing.
#8 Sheet Metal Screws
(3 per joint)
Sealant
Storm Collar
TWL101a
TWL101a
Twist Lock Pipe
2/8/99 djt
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rfsdv34

Table of Contents