HORNER HE200WCM910 User Manual page 40

Wireless communication rs-232/485 rf modem
Table of Contents

Advertisement

Page 40 
 
 
NB (Parity) Command
<Serial Interfacing> Select/Read parity settings
for UART communications.
PK (Maximum RF Packet Size) Command
<RF Interfacing> PK Command is used to
set/read the maximum size of RF packets. The
maximum packet size can be used along with
RB/RO to implicitly set the channel dwell time.
If PK is set above 256 and BR is subsequently
changed to 0, then PK will automatically be
lowered to 256 and a warning will be raised (see
BR (RD Data Rate) and WN (Warning Data)
Commands for details).
Changes to this parameter may have a secondary effect on the RB (Packet Control Characters)
Parameter. RB must always be less than or equal to PK. If PK is changed to a value less than the
current value of RB, RB is automatically lowered to be equal to PK.
* When BR = 0, the maximum PK value is 0x100 (256d). When BR = 1, the maximum PK value
is 0x800 (2048d).
PL (Power Level) Command
<RF Interfacing> PL Command is used to
set/read the power level at which the modem
transmits.
 
 
 
 
RS‐232/485 RF Modem Product Manual – MAN0782‐02 
AT Command: ATNB
Binary Command: 0x23 (35 decimal)
Parameter Range: 0 – 4
Parameter
Default Parameter Value: 0
Number of bytes returned: 1
AT Command: ATPK
Binary Command: 0x29 (41 decimal)
Parameter Range: 0 – 0x800 [Bytes]
Default Parameter Value: 0x800*
Number of bytes returned: 2
Related Commands: BR (RF Data Rate) RB
(Packetization Threshold), RO (Packetization
Timeout), WN (Warning Data)
AT Command: ATPL
Binary Command: 0x3A (58 decimal)
Parameter Range: 0 – 4
Parameter
Default Parameter Value: 4
Number of bytes returned: 1
Configuration
Value
8-bit (no parity or
0
7-bit (any parity)
1
8-bit even
2
8-bit odd
3
8-bit mark
4
8-bit space
(2048 decimal)
Configuration
Value
0
1 mW
1
10 mW
2
100 mW
3
500 mW
4
1000 mW (1 Watt)