Error Codes

The SJ200
series inverters will trip on over-current, over-voltage, and
2
under-voltage to protect the inverter. The motor output turns OFF, allow-
ing the motor to free-run to a stop. Press the Stop/Reset key to reset the
inverter and clear the error.
Basic Error Codes
Error
Code
Over current event while at
E01
constant speed
E02
Over current event during
deceleration
Over current event during
E03
acceleration
E04
Over current event for other
conditions
E05
Overload protection
Braking resistor overload
E06
E07
Over voltage protection
EEPROM error
E08
Under-voltage error
E09
E11
CPU error
E22
External trip
E12
USP (Unattended Start
E13
Protection)
E14
Ground fault
E15
Input over-voltage
Inverter thermal trip
E21
Name
Probable Cause(s)
• Inverter output was short-circuited
• Motor shaft is locked
• Load is too heavy
• A dual-voltage motor is wired
incorrectly
Note: The SJ200
nominally 200% of rated current
• DC braking power(A054) set too high
• Current transformer / noise error
• Motor overload is detected by the
electronic thermal function
• Regenerative braking resistor exceeds
the usage time or usage ratio
• DC bus voltage exceeds a threshold,
due to regenerative energy from motor
• Built-in EEPROM memory experi-
enced noise, high temperature, etc.
• DC bus voltage decreased enough to
cause a control circuit fault
• Built-in CPU had internal error
• [EXT] input signal detected
• When (USP) was enabled, an error
occurred when power was applied while
a Run signal was present
• A ground fault was detected between
the inverter output and the motor. This
feature protects the inverter, and does not
protect humans.
• Input voltage was higher than specified
value, after 60 sec. in Stop Mode
• Inverter internal temperature is above
the threshold
13
will over current trip at
2