3. Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
However it can be selected 2°C higher or 2°C lower from standard set temperature by pressing the "Room Temperature Setting
button".
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX6 at
indoor electronic controller.
7.5.
Sleep Mode Auto Operation
Cooling or Soft Dry Operation
Purpose is to obtain a comfortable room temperature while
sleeping. When you press the SLEEP Mode, the following
movement will start to avoid overcooling.
• Sleep shift operation starts, when the room temperature
reaches the setting temperature or after 1 hour of operation.
• The setting temperature will be risen by 0.5°C at the start of
operation and by 0.5°C one hour later .
• The airflow volume will automatically change to Lo- fan
speed.
• Sleep Mode operation time is 8 hours, the operation will be
stop after 8 hour.
• When used together with the Timer, the Timer has priority.
Judgement
23°C
Cooling
Heating
23°C
Soft Dry
Heating
Cooling
23°C
Heating
Operation
Cooling
Soft Dry
Heating
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
Next Mode
Cooling
Soft Dry
O
(Judgement:
Not Applicable
23°C & Above)
Not Applicable
(Judgement:
23°C & Above)
O
(Judgement:
Not Applicable
23°C & Above)
Hi
(Standard)
(+2°C)
(±0°C)
27°C
25°C
24°C
22°C
23°C
21°C
31
Heating
O
(Judgement:
Below 23°C)
O
O
(Judgement:
Below 23°C)
O
(Judgement:
Below 23°C)
Lo
(-2°C)
23°C
20°C
19°C