Voltronic Power 6K User Manual
Voltronic Power 6K User Manual

Voltronic Power 6K User Manual

Tower online ups
Hide thumbs Also See for 6K:

Advertisement

Quick Links

User Manual
6K/10K Rack/Tower Online UPS
Uninterruptible Power Supply System

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 6K and is the answer not in the manual?

Questions and answers

Summary of Contents for Voltronic Power 6K

  • Page 1 User Manual 6K/10K Rack/Tower Online UPS Uninterruptible Power Supply System...
  • Page 2 Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
  • Page 3: Table Of Contents

    Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ....................1 1-1. T ....................... 1 RANSPORTATION AND TORAGE 1-2. P ............................1 REPARATION 1-3. I ............................1 NSTALLATION 1-4. O ............................2 PERATION 1-5. S ............................2 TANDARDS 2. INSTALLATION ..........................3 2-1.
  • Page 4: Safety And Emc Instructions

    1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact.
  • Page 5: Operation

    1-4. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads. If the external battery cabinet is connected, the UPS output Anderson connector may be electrically live even if the UPS system is not connected to the building wiring outlet.
  • Page 6: Installation

    2. Installation There are two types: standard and long-run models. Please refer to the following model table. Model Type Model Type 6KRT Standard model 6KRTL Long-run model 10KRT Standard model 10KRTL Long-run model 2-1. Unpacking and Inspection Unpack the package and check the package contents. The shipping package contains: ●...
  • Page 7 Diagram 3: Battery Pack Rear Panel 1. RS-232 communication port 2. USB communication port 3. EPO (Emergency Power Off) connector 4. Share current port (for parallel function) 5. Parallel port (for parallel function) 6. Intelligent slot 7. EMBS (External Maintain Bypass Switch) port 8.
  • Page 8: Rack/Tower Installation

    2-3. Rack/Tower Installation 2-3-1 Tower Installation The UPS system is shipped with two sets of feet and 6 extensions (2 short extensions plus 4 long extensions) that can be used to tower install the UPS module in 3U or UPS module with one battery bank in 6U. Install UPS module in 3U Step 1 Step 2...
  • Page 9: Single Ups Installation

    2-3-2 Rack Installation Please follow below steps to mount UPS into 19” rack or rack enclosure. Step 1: Attach mounting ears to the side Chart 1 mounting holes of UPS using the screws provided and the ears should face forward. Please refer to chart 1.
  • Page 10: Parallel Ups Installation

    Warning: ● For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for other external battery pack, make sure a DC breaker or other protection device between UPS and external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before installation.
  • Page 11: Operations

    3. Operations 3-1. Operating Mode/Status Description Mode/Status Description UPS Power On When UPS is powered on, it will enter into this mode for a few seconds for initializing the CPU and system. AC Mode When the input voltage is within acceptable range, and the UPS is turned on (the inverter is running), the UPS will provide pure and stable sine wave...
  • Page 12: Led Indicators

     Press this button to select the previous item in the menu.  Or press this button to jump to previous page in the screen.  Or press this button to increase the number in the setting.  Press this button to select the next item in the menu. DOWN ...
  • Page 13 3-5-2. Turn on the UPS without utility power supply (to Battery mode) 1) Make sure the battery is connected well and the battery pack breaker is at “ON” position; 2) Press the “ON/ENTER” button to start up the internal power, the UPS will enter into bypass mode without output;...
  • Page 14 4) The backup time may change under different environment temperature and load type; 5) The maximum backup time is limited by default 16.5 hours (After discharging 16.5 hours, UPS will shut down automatically to protect the battery). The time could be modified through LCD panel or communication port.
  • Page 15: Parallel Ups Operation

    3-6. Parallel UPS Operation For parallel UPS operation, please contact your dealer for more professional support. 3-7. LCD Operation The entire LCD structure is demonstrated as diagram below: Turn On Press button“Enter” Batt Test Control Press button“Esc” Mute Para Unlock Page 1: Input Page 2: Output Press button“Enter”...
  • Page 16: Main Interface (Home Page)

    3-7-1. Main interface (home page) 1) In the first line, it will display the UPS running status mode; 2) When alarms happen, the warning or fault information will display below the “load” line; 3) When the front panel is not operated for 10 minutes, the display page will return back to home page; 4) Press the “UP”...
  • Page 17 Generally speaking, these two messages will not be displayed at the same time or in all operation modes. 1) Turn On/Turn Off This item is for turning on/off the UPS; a) On Bypass mode, it will display “Turn On” in control menu. If it is selected and confirmed, the UPS will transfer to AC mode or converter mode or ECO mode or battery mode according to the setting and input status.
  • Page 18 3) Mute It is to mute the buzzer only when UPS is in battery/bypass/fault mode. After the selection is confirmed, it will return back to home page and mute icon will be displayed. Although this selection will display in other modes, it can’t be mute alarm and reminder will pop up at the same time. →...
  • Page 19 3-7-2-4. Information Information displays all parameter setting value and status. Press “UP” or “DOWN” to explore the pages. 3-7-2-5. Setting This menu is used to configure the parameter settings or do the calibrations. NOTE: Some settings will be only available in some operation modes. If the setting is not available in current mode, the LCD will show prompt message with “Item can not be set in this mode”.
  • Page 20 1) Bypass setting Interface Description 1. Status (only available in bypass / AC mode) 1.1 Open/Forbid: Open: Bypass allowed. When selected, UPS will run at Bypass mode depending on bypass enabled/disabled setting. Forbid: Bypass not allowed. When selected, it’s not allowed for running in Bypass mode under any situations.
  • Page 21 3) Output setting (only available or effective on bypass mode) Interface Description 1. Volt: 208: Presenting the rated output voltage with 208Vac 220: Presenting the rated output voltage with 220Vac 230: Presenting the rated output voltage with 230Vac 240: Presenting the rated output voltage with 240Vac 2.
  • Page 22 5) Calibration Interface Description 1. Batt: Calibrate the battery voltage measurement. Calibration range is from 0V to 5.7V. The default value is 0V. It is available on all operation modes. 2. Inv: Adjust the inverter output voltage; the adjustable range is from 0V to 6.4V, the default value is 0V.
  • Page 23 Backup Time Parameters Setting: Batt Groups: Set the number of battery group ranging from 1 to 6. The default value is 1 group; Batt Cap: Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26AH, 40AH, 65AH, 100AH and so on. The default value is 9AH. Factor: Calibrate the displayed backup time by adjusting this multiplier factor.
  • Page 24: Trouble Shooting

    4. Trouble Shooting 4-1. Warning status When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems with UPS. Users can see the warning code from LCD panel and refer to the trouble shooting table to check what problem probably happen.
  • Page 25 Warning 10: IP Fuse Open Input fuse on the power stage Check and replace the input board is burnt. fuse. Warning 33: Overload 3Times Locked in bypass after overload 3 Remove excess loads from UPS times in 30 minutes. output first. Then, shut down the UPS and restart it.
  • Page 26 Fault 14: Output Short Short circuit occurs on the UPS Remove short circuit. output. Fault 1A: NegPower UPS output power is negative. It Contact the dealer. means there is energy feedback into the internal of UPS from output. It may be caused by regenerative load current...
  • Page 27: Storage And Maintenance

    5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months...
  • Page 28: Specifications

    6. Specifications MODEL 6KRT(L) 10KRT(L) CAPACITY* 6000 VA / 5400 W 10000 VA / 9000 W INPUT 110 VAC ± 3 % at 50% Load; Low Line Loss 176 VAC ± 3 % at 100% Load Voltage Low Line Comeback Low Line Loss Voltage + 10V Range High Line Loss...