Summary of Contents for Voltronic Power Galleon One 6K
Page 1
User Manual PF 1 6K/10K Online UPS Uninterruptible Power Supply System Version: 1.1...
Page 2
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ......................... 1 1-1. T RANSPORTATION AND TORAGE ........................... 1 1-2. P REPARATION ................................1 1-3. I NSTALLATION ................................1 1-4............................ 2 ONNECTION ARNINGS 1-5. O PERATION ................................... 3 1-6. S TANDARDS ...................................
1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and Storage Please transport the UPS system only in the original package to protect against shock and impact.
1-4. Connection Warnings • There is no standard backfeed protection inside of the UPS. Please isolate the UPS before working according to Diagram 1. The isolation device must be able to carry the UPS input current. Diagram 1: External backfeed protection wiring •...
1-5. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table. Model Type Model Type standard model Long-run model 10KL Parallel function is also available for these two types and related installation and operation of Parallel function will be described in detail in the following content.
2-3. Single UPS Installation Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
Warning: (Only for standard model) ● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection. ● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal battery to the external battery.
6) Refer to the following wiring diagram: Diagram 1: Power cable connection Diagram2: Wiring diagram of parallel system 2-5. Software Installation For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
3. Operations 3-1. Button Operation Button Function Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS. ON/Enter Button Enter Key: Press this button to confirm the selection in setting menu. ...
LCD Panel: Display Function Backup time information Indicates battery discharge time in numbers. H: hours, M: minutes, S: seconds Fault information Indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in details in section 3-9. Mute operation Indicates that the UPS alarm is disabled.
3-3. Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second Others Beeping once every second Fault Beeping continuously 3-4.
Page 14
total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system safety. 5) If the overload time is longer than acceptable time listed in spec at AC mode, the UPS will automatically transfer to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is longer than acceptable time listed in spec at Battery mode, the UPS will become fault status.
Page 15
NOTE 2: After turning off the UPS, please be aware that the UPS is working at Bypass mode and there is risk of power loss for connected devices. 2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the input breaker.
Note: 0 = no jumper; 1 = connect with jumper; x = the pins are for other functions. 5) Modify the battery pack to meet the setting number in control board carefully. 6) Modify charger voltage according to below table to meet the setting number in control board. There are 5 jumpers on the charger board.
Page 17
Turn off each UPS (Refer to section 3-4-7.). Then, follow the wiring procedure in section 2-4. Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one with the parallel cable and share current cable, and then screw the cover back. 3-5-2.
5) Set the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back. Turn on the remaining UPSs and finish the parallel system connection. Warning: (Only for the parallel system) ● Before turning on the parallel system to activate inverter, make sure that all unit’s maintenance switch at the same position.
3-7. LCD Setting Parameter 1 Parameter 2 There are two parameters to set up the UPS. Parameter 1: It’s for program alternatives or setting options. Refer to below table. Parameter 2 is the setting values for each program. Programs available list for parameter 1: Bypass/ Battery Code...
Page 20
02: Output frequency Interface Setting Parameter 2: Output Frequency Setting the output frequency. You may choose following three 60 Hz, CVCF mode options in parameter 2: 50.0Hz: The output frequency is setting for 50.0Hz. 60.0Hz: The output frequency is setting for 60.0Hz. At: If selected, output frequency will be decided according to the latest normal utility frequency.
Page 21
04: Frequency range for bypass Interface Setting Parameter 1 & 2: Setting acceptable frequency range for bypass mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter”...
Page 22
07: Frequency range for ECO mode Interface Setting Parameter 1 & 2: Setting acceptable frequency range for ECO mode. You have to set up the range by setting high and low points. When it shows “LLS” in parameter 2, please press “Enter” key and it will show “LS”...
Page 23
10: Reserved Interface Setting Reserved 11: Reserved Interface Setting Reserved 12: Hot standby function enable/disable Interface Setting Parameter 2: Enable or disable Hot standby function. You may choose following two options in Parameter 2: YES: Hot standby function is enabled. It means that the current UPS is set to host of the hot standby function, and it will restart after AC recovery even without battery connected.
Page 24
14: Charger voltage adjustment Interface Setting After it shows “14” in parameter 1, please press “Enter” key first. Then, you may choose Ad or SU to adjust charger voltage in parameter 1 by pressing “Up” or “Down” key. After pressing “Enter”...
17: Reserved Interface Setting Reserved 3-8. Operating Mode/Status Description If parallel UPS systems are successfully set up. The master UPS will be default assigned as “001” and slave UPSs will be assigned as either “002” or “003”. The assigned numbers may be changed dynamically in the operation.
Page 26
CVCF mode Description When input frequency is within 46 to 64Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode. LCD display Battery mode Description When the input voltage is beyond the acceptable range or power failure, UPS will backup power from battery and alarm will beep every 4 seconds.
Battery Test Description When UPS is in AC mode or CVCF mode, press “Test” key for more than 0.5s. Then the UPS will beep once and start “Battery Test”. The line between I/P and inverter icons will blink to remind users. This operation is used to check the battery status.
3-10. Warning Indicator Warning Icon (flashing) Alarm Overload Beeping twice every second Overcharge Beeping every second EPO enable Beeping every second Fan failure/Over temperature Beeping every second Charger failure Beeping every second I/P fuse broken Beeping every second Overload 3 times in 30min Beeping every second Battery unconnected Beeping every second...
4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm in the front The AC input power is not Check if input cable firmly display panel even though the mains is connected well.
5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months...
6. Specifications MODEL 10KL CAPACITY* 6000 VA / 6000 W 10000 VA / 10000 W INPUT 110~300Vac @ (0~60%) Load Line Loss 140~300V @ (60~80%) Load 176~300Vac @(80~100%)Load Voltage Range Low Line Comeback Low Line Loss Voltage + 10V High Line Comeback High Line Loss Voltage - 10V 46Hz ~ 54 Hz @ 50Hz system Frequency Range...