1. Important Safety Warning Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
1-5. Maintenance, service and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1. Rear panel view IEC Type Schuko Type India Type NEMA Type 1.
Page 6
This intelligent slot is perfect for SNMP, RS-232, USB or AS-400 card. When installing with communication card in the UPS, it will provide advanced communication and monitoring options. Step 1: Step 2: Step 3: Remove cover of intelligent Insert communication card Screw card tightly and slot.
Page 7
Step 8: External battery capacity configuration in software To calculate accurate backup time of external batteries, it’s necessary to configure battery numbers in software. The standard calculated capacity for one battery is 9Ah. If connecting to 100Ah batteries, then it’s equal to 11 in parallel (100Ah / 9Ah ≈ 11 sets).
3. Operations 3-1. Button operation Button Function Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS. Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.
3-2. LCD Panel Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minute, S: second Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3-5 section.
Battery information Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is fault. Indicates low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage or frequency. Indicates battery voltage. Vac: Input voltage, Hz: input frequency, Vdc: battery voltage Indicates battery charge/discharge voltage 3-3.
3-5. UPS Setting There are three parameters to set up the UPS. Parameter 1 Parameter 1: It’s for program alternatives. There are 6 programs to set up. Refer to below table. Parameter 2 and parameter 3 are the setting options or values for each program.
Page 12
03: Bypass mode enable/disable Interface Setting Parameter 3: Enable or disable Bypass function. You may choose the following two options: ENA: Bypass mode enable DIS: Bypass mode disable 04: Bypass voltage range setting Interface Setting Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key.
06: Backup time setting for outlets Interface Setting Parameter 3: Set up backup time on battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. 0: When setting as “0”, the backup time will be only 10 seconds.
3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail Inverter voltage Low Bus over Inverter output short Bus under Battery voltage too high Bus unbalance Battery voltage too low Inverter soft start fail Over temperature Inverter voltage high Overload...
4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the mains is normal. connected well.
Page 16
Symptom Possible cause Remedy Fault code is shown as 1, 2, 3, 4, A UPS internal fault has Contact your dealer 11, 12, 13 and 41 on LCD display occurred. There are two and alarm is continuously possible results: sounding. 1.
5. Storage and Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
6. Specifications CAPACITY* 1000 VA / 800 W INPUT Nominal input voltage 88-144 VAC and 176 - 288 VAC (Auto sensing) Frequency Range 40 ~ 70 Hz (Auto sensing) Phase Single phase with ground ≧ 0.99 Power Factor OUTPUT Output voltage 110/115/120/127VAC or 208/220/230/240 VAC AC Voltage Regulation ±...